Siemens Power Supply - SITOP PSU100S 6EP1332-2BA20
Manufacturer:
Siemens
Product No.:
6EP1332-2BA20
Condition:
In Stock
Product Type:
Power Supply
Product Origin:
USA
Weight:
500g
Shipping port:
Xiamen
Warranty:
12 months
UBEST – Vertrauenswürdiger globaler Lieferant für Automatisierungsteile
Wir bieten eine große Auswahl an vorrätigen Ersatzteilen für die industrielle Automatisierung. Alle Produkte haben eine 12-monatige Garantie und eine 30-tägige Rückerstattung bei Qualitätsproblemen.
SITOP PSU100S 24VDC/2.5A Power Supply: Compact and Reliable Performance
Input Power Specifications
- Input Voltage Range: 85-132V AC for 120V systems
- Wide Input Capability: 170-264V AC for 230V operation
- Frequency Range: 47-63 Hz automatic adaptation
- Current Consumption: 1.25A at 120V, 0.74A at 230V input
- Inrush Current Limit: Maximum 33A with 0.4 A²·s I²t value
- Power Buffering: 20ms hold-up during voltage drops
Output Performance Characteristics
- Stable DC Output: 24V DC nominal voltage rating
- Adjustable Range: 22.8V to 28V via potentiometer control
- Current Capacity: 2.5A continuous, 3A up to 45°C
- Voltage Precision: 3% overall tolerance for consistent performance
- Ripple & Noise: 30mV typical, 150mV maximum residual ripple
- Response Time: 15ms typical voltage rise time
Protection & Safety Features
- Overvoltage Protection: Internal cutoff below 33V output
- Short-Circuit Proof: Constant current characteristic protection
- Overload Capability: 150% rated current for 5 seconds
- Current Limiting: 3.0-3.4A response range for fault conditions
- Isolation Rating: SELV output per EN 60950-1 safety standards
- Protection Class: IP20 for basic environmental protection
Efficiency & Thermal Management
- High Efficiency: 85% typical energy conversion rate
- Power Output: 60W typical delivered active power
- Heat Dissipation: 10W typical power loss during operation
- Temperature Derating: 3% per Kelvin above 60°C ambient
- Parallel Operation: Supports 2 units for increased power
- MTBF Rating: 1,804,044 hours at 40°C ambient temperature
Environmental Specifications
- Operating Temperature: -25°C to +70°C wide range capability
- Storage Conditions: -40°C to +85°C for transport and storage
- Humidity Range: 5-95% non-condensing relative humidity
- Climate Classification: IEC 60721 3K3 environmental category
- Marine Approval: BV and DNV shipbuilding certifications
- EMC Compliance: EN 61000-6-2 immunity and EN 55022 emission
Physical & Installation Data
- Compact Dimensions: 32.5mm × 125mm × 120mm (W×H×D)
- Installation Width: 32.5mm for space-efficient mounting
- Mounting Height: 225mm including connection space
- Lightweight Design: 0.32kg for easy handling
- DIN Rail Mounting: EN 60715 35x7.5/15 snap-on installation
- Wire Range: 0.5-2.5mm² for input and output connections
Monitoring & Indicators
- Status Display: Green LED for 24V OK visual indication
- Relay Contact: NO contact for remote monitoring (60V DC/0.3A)
- Response Delay: Maximum 0.3s for status signal activation
- Overshoot Protection: Less than 3% when switching on
- Load Step Response: 1ms settling time for 10-90% changes
- Voltage Stability: 0.1% regulation for input fluctuations
Package Contents
- Complete 6EP1332-2BA20 power supply unit
- DIN rail mounting clip and installation accessories
- Operation manual and technical data sheet
- Wiring diagram and connection guide
- Pale turquoise device identification labels
Shipping & Delivery
- FedEx express international shipping available
- UPS worldwide expedited delivery options
- DHL global air freight services offered
- Secure professional packaging materials
- Quick order processing within 24 hours
Technical Application Questions
- What is the main advantage of this power supply's compact design?
- The 32.5mm width allows high-density installation in control cabinets with limited space
- How does the temperature derating affect practical applications?
- Above 45°C ambient, the output current gradually reduces to maintain reliable operation
- Can I use this unit in parallel configuration for redundancy?
- Yes, two units can operate in parallel with proper bridging for increased reliability
- What maintenance schedule ensures long-term reliability?
- Annual inspection of terminals and cleaning of ventilation paths maintains optimal performance
- How do I interpret the status relay contact signals?
- The normally open contact closes when output voltage is within specification for remote monitoring
© 2025 Ubest Automation Limited. All rights reserved.
Original Source: https://www.ubestplc.com/
Contact: sales@ubestplc.com Phone: +86 180 3000 5825