F3237 HIMA Safety Input Module | NAMUR Sensor Interface

Σε απόθεμα - 14 τεμάχια διαθέσιμα
Manufacturer:
HIMA
Condition:
In Stock
Product Type:
Safety Input Module
Weight:
500g
Shipping port:
Xiamen
Warranty:
12 months

UBEST – Αξιόπιστος Παγκόσμιος Προμηθευτής Ανταλλακτικών Αυτοματισμού

Προσφέρουμε μια μεγάλη γκάμα διαθέσιμων ανταλλακτικών βιομηχανικού αυτοματισμού. Όλα τα προϊόντα συνοδεύονται από 12μηνη εγγύηση και 30ήμερη επιστροφή χρημάτων για θέματα ποιότητας.

Σχετικά με εμάς | Επικοινωνία

HIMA F3237 Safety Input Module: 8-Channel NAMUR Sensor Interface

The HIMA F 3237 safety input module provides reliable monitoring for critical industrial sensors. This eight-channel module connects safety-rated proximity switches and NAMUR sensors with precision. It continuously monitors all connected lines for short-circuits and wire breaks during operation. The F 3237 module supports requirement classes AK 1 through AK 6 for versatile applications. It delivers comprehensive self-testing capabilities and ensures operational safety in demanding environments.

Core Safety & Certification Specifications

  • Brand: HIMA Safety Systems
  • Model: F 3237 8-Channel Input Module
  • Safety Standard: Compliant with DIN 19234 (NAMUR)
  • Requirement Class: AK 1 to AK 6 comprehensive coverage
  • Safety Rating: Suitable for safety instrumented systems
  • Channel Count: Eight independent safety input channels
  • Response Time: Approximately 10 milliseconds per channel
  • Self-Testing: Continuous automatic diagnostic monitoring

Electrical Characteristics & Performance

  • Supply Voltage: 8.2 VDC regulated sensor supply
  • Current Consumption: 5V at 90 mA, 24V at 170 mA
  • Line Impedance: Maximum 50 Ohms per DIN 19234
  • Shunt Resistor: 681 Ohm, 1% tolerance, 0.25W rating
  • Operating Temperature: -20°C to +70°C industrial range
  • Storage Temperature: -40°C to +85°C extended capability
  • Humidity Range: 5% to 95% non-condensing operation
  • Vibration Resistance: 2G operational, 5G non-operational

Signal Monitoring & Threshold Values

  • 0-Signal Range: 0.35 mA to 1.2 mA input current
  • 1-Signal Range: 2.1 mA to 6.0 mA input current
  • Wire Break Detection: Below 0.28 mA threshold
  • Short-Circuit Detection: Above 6.5 mA threshold
  • Input Filtering: Digital filtering for noise immunity
  • Signal Accuracy: ±1% typical current measurement
  • Update Rate: 100 Hz per channel sampling frequency
  • Isolation: Channel-to-channel 500V AC isolation

Installation & Wiring Specifications

  • Maximum Cable Length: 1000 meters with 0.5mm² wire
  • Wire Gauge: 0.5mm² to 2.5mm² compatible
  • Connection Type: Screw terminal block connections
  • Space Requirement: 4 TE (Terminal Equipment units)
  • Mounting: Standard DIN rail 35mm compatible
  • Weight: Approximately 350 grams complete unit
  • Certification: CE, UL, ATEX compatible design
  • Enclosure Rating: IP20 for control cabinet installation

Compatibility & Sensor Support

  • Sensor Types: NAMUR proximity switches per DIN 19234
  • Resistor Sensors: Compatible with resistor-wired sensors
  • Third-Party Sensors: Support for P&F and other brands
  • Custom Configuration: 47 kΩ resistor option available
  • Output Current: Configurable up to 170 μA minimum
  • Software Block: HB-RTE building block integration
  • System Integration: HIMA safety system compatibility
  • Backplane Communication: Standard HIMA bus system

Packaging & Delivery Information

  • Package Contents: One HIMA F 3237 input module unit
  • Documentation: Installation guide and technical manual
  • Shipping Options: FedEx, UPS, DHL express delivery
  • Packaging: Industrial-grade protective materials
  • Delivery Time: 3-5 business days for stock items
  • Warranty Coverage: 12 months quality assurance

Technical FAQ

  • What types of sensors does this module support?
    The module supports NAMUR proximity switches, resistor-wired sensors, and safety-rated proximity switches.
  • How does the module detect wiring problems?
    It continuously monitors current levels to detect wire breaks below 0.28 mA and short-circuits above 6.5 mA.
  • What is the maximum cable length supported?
    The system supports cable lengths up to 1000 meters using 0.5mm² wire gauge.
  • Can I use non-NAMUR sensors with this module?
    Yes, with appropriate external resistors to adjust current levels for proper detection.
  • What diagnostic features does the module include?
    It provides continuous self-testing including input filtering, cross-talk checking, and function verification.

© 2025 Ubest Automation Limited. All rights reserved.