E82ZAFCC201 Lenze Function Module | 8200 Series I/O
Manufacturer:
Lenze
Product No.:
E82ZAFCC201
Condition:
In Stock
Product Type:
Function Modules
Product Origin:
DE
Weight:
200g
Shipping port:
Xiamen
Warranty:
12 months
UBEST – Pembekal Alat Ganti Automasi Global yang Dipercayai
Kami menawarkan pelbagai alat ganti automasi industri yang tersedia dalam stok. Semua produk datang dengan jaminan 12 bulan dan pemulangan wang dalam 30 hari untuk isu kualiti.
E82ZAFCC201 Function Module: Reliable I/O for Lenze 8200-Series Drives
Key Technical Specifications
- Brand & Model: Lenze E82ZAFCC201 function module for 8200-series drives.
- Cable Type: Requires shielded pair cable with 120Ω impedance (95 to 140Ω range).
- Signal Delay: 5 ns/m typical propagation time.
- Input Resistance (X3.2/E1): 3.3 kΩ. LOW = 0-3V (HTL), HIGH = 12-30V (HTL).
- Frequency Input (E1): Configurable via C0425 – 0-10 kHz (single channel) or 0-1 kHz (dual channel).
- Drive Inhibit (CINH) on X3.3/28: Input resistance 3.3 kΩ. RUN = HIGH (12-30V), STOP = LOW (0-3V).
- Reference Voltage (X3.3/20): U = 20V. Max load 0.6W.
Cable Length & Wire Size Guidelines
- Cable length ≤ 300 m: Use 0.25 - 0.34 mm² (AWG22) with resistance ≤ 70Ω/km.
- Cable length 301 - 1000 m: Use 0.5 mm² (AWG20) with resistance ≤ 40Ω/km.
- Always use shielded twisted pair cable for reliable signal transmission.
Terminal Connection Specifications (X3.2 / X3.3)
- X3.2 / E1* (Frequency Input): Reference = GND2. HTL level (0-3V LOW, 12-30V HIGH).
- X3.3 / 7 (Reference Potential 1): Common ground reference for inputs.
- X3.3 / 39 (Reference Potential 2): Dedicated reference for drive inhibit (CINH).
- X3.3 / 28 (Drive Inhibit Input): Enables or disables the drive. HIGH = run, LOW = stop.
- X3.3 / 20 (Auxiliary Voltage Output): Supplies 20V DC at max 0.6W for external sensors.
Frequently Asked Questions (FAQ)
-
Q: Which drives work with the E82ZAFCC201 module?
A: This module fits Lenze 8200-series drives. Check your drive model for compatibility. -
Q: What cable type does the E82ZAFCC201 require?
A: You need a shielded twisted pair cable with 120Ω characteristic impedance. -
Q: Can I use this module for high-speed counting?
A: Yes. The frequency input supports 0-10 kHz single channel or 0-1 kHz dual channel via C0425. -
Q: What voltage levels does the drive inhibit input accept?
A: HIGH (12-30V) = drive runs. LOW (0-3V) = drive stops. Input resistance is 3.3 kΩ. -
Q: Is the E82ZAFCC201 still in production?
A: No. Lenze marks this product as Phase-Out. We offer remaining stock while available. -
Q: What is the maximum cable length for reliable operation?
A: Up to 1000 meters using 0.5 mm² (AWG20) shielded cable. Keep total resistance within limits.