{"product_id":"10001-r-1-honeywell-vertical-bus-driver","title":"10001\/R\/1 Honeywell Vertical Bus Driver","description":"\u003ch3\u003eHoneywell 10001\/R\/1 Vertical Bus Driver Specifications and Description\u003c\/h3\u003e\u003ch3\u003eDescription\u003c\/h3\u003e\u003cp\u003eThe 10001\/R\/1 Vertical Bus Driver (VBD) module is a critical component within the Central Part (CP) of the FSC system, connecting it to the I\/O level. This module is installed in the Central Part rack, with a maximum of 14 vertical bus drivers per CP. Each VBD supports up to 10 Horizontal Bus Driver (HBD) modules. The maximum distance between a VBD and any I\/O rack on the vertical bus is 5 meters (16.4 feet). The VBD modules are used for establishing communication between the central processor and I\/O modules in the system.\u003c\/p\u003e\u003ch3\u003e\u003cstrong\u003eTechnical Data\u003c\/strong\u003e\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eType Number:\u003c\/strong\u003e 10001\/R\/1\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eApprovals:\u003c\/strong\u003e CE, TÜV, UL\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSoftware Versions:\u003c\/strong\u003e Compatible with all versions\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSpace Requirements:\u003c\/strong\u003e 4 TE, 3 HE (4 HP, 3U)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePower Requirements:\u003c\/strong\u003e 5 Vdc, 275 mA\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRipple Content:\u003c\/strong\u003e Less than 50 mV p-p\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch3\u003e\n\u003cstrong\u003eModule Components\u003c\/strong\u003e The 10001\/R\/1 module consists of two main parts:\u003c\/h3\u003e\u003col\u003e\n\u003cli\u003e\n\u003cstrong\u003eElectronic Part (Mainboard):\u003c\/strong\u003e This part includes all the necessary electronics for the module's operation.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWiring Part (10001\/A\/1):\u003c\/strong\u003e This part is secured to the 19-inch rack with bolts on the 96-pin connector, allowing for the exchange of the electronic part without disconnecting the vertical bus flat cable.\u003c\/li\u003e\n\u003c\/ol\u003e\u003ch3\u003e\u003cstrong\u003eApplications\u003c\/strong\u003e\u003c\/h3\u003e\u003cp\u003eThe 10001\/R\/1 VBD module can be used in various configurations:\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eNon-redundant CP and Non-redundant I\/O:\u003c\/strong\u003e Either 10001\/1\/1 or 10001\/R\/1 can be used.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRedundant CP and Non-redundant I\/O:\u003c\/strong\u003e Only 10001\/R\/1 can be used due to its relay which disconnects the VBD from the vertical bus in case of a CP shutdown, either through an onboard watchdog on the VBD or via software.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":49196523520282,"sku":"10001\/R\/1","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0873\/6240\/4634\/files\/FSC10002-1-2Module.jpg?v=1718708414","url":"https:\/\/www.ubestplc.com\/products\/10001-r-1-honeywell-vertical-bus-driver","provider":"Ubest Automation Limited","version":"1.0","type":"link"}