10101/2/1 | Honeywell FSC Fail-safe Digital Input Module
Manufacturer:
Honeywell
Product No.:
10101/2/1
Condition:
In Stock
Product Type:
Digital Input Module
Product Origin:
USA
Weight:
300g
Shipping port:
Xiamen
Warranty:
12 months
UBEST – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Honeywell 10101/1/2 16-Channel Digital Input Module
Overview
The Honeywell 10101/1/2 is a fail-safe digital input module designed for industrial applications. It supports sixteen 60 Vdc digital input channels, making it suitable for various safety-critical systems.
Technical Specifications
- Type Number: 10101/1/2
- Approvals: CE, TÜV, UL
- Software Versions: ≥ 2.80b
- Space Requirements: 4 TE, 3 HE (4 HP, 3U)
Power Requirements
- 5 Vdc: 8 mA
- 24 Vdc (internal supply only): 2 x 40 mA
- 60 Vdc (input currents): 2 x 27 mA
- Ripple Content (on 5 Vdc): < 0.5 Vp-p (0-360 Hz)
Input Specifications
- Number of Input Channels: 16 (divided into 2 isolated groups of 8)
- Input Voltage: Typically 60 Vdc, Maximum 85 Vdc
- Input Current: 3.3 mA at 60 Vdc
- Input HIGH Voltage: > 40 Vdc
- Input LOW Voltage: < 20 Vdc (I < 1 mA)
- Input Delay: Typically 10 ms
Fuses
- Fuse Values: 2 x 100 mA
- Fuse Type: Round, TR5-F/19370K
- Fuse Dimensions: ∅ 8.2 mm (0.32 in), Height 7.7 mm (0.3 in)
Key Coding
- Module Code: Hole A15, Pins C3, C11, C23
- Rack Code: Blind Stops C19, C27, C31, Large Pins A15
Additional Notes
- Fail-to-Safe Nature: The input stage is designed to de-energize the input signal to the processor in the event of a component failure, ensuring a safe condition in a normally energized system.
- Self-Test Functions: The module's remaining logic circuitry is covered by the system's self-test functions, ensuring the ability to receive logic level '0' and '1' signals and detect crosstalk between inputs.
- Supply Circuitry: The module features two galvanically isolated groups of eight inputs each, allowing for independent power supply groups to support segregation in process units and subunits.
- Common 0 Vdc Connection: The 24 Vdc (internal) and 60 Vdc (external) must share a common 0 Vdc connection.