1756-OW16I ControlLogix 16 Pt Digital Relay Module | Allen-Bradley
UBEST – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
ControlLogix 1756-OW16I Module Overview
The ControlLogix 1756-OW16I is a 16-point digital relay module designed to operate within ControlLogix systems, offering reliable and efficient control over various industrial processes.
Electrical Specifications
- Supply Voltage: DC
- Input Voltage Type: DC
- Digital Output Type: Relay
- Electric Connection Type: Screw connection
- Bounce Time: Mean of 1.2 μs
- Total Backplane Power: 4.4 W
- Thermal Dissipation: 15.35 BTU/h
- Current Draw: 150 mA @ 5.1V, 150 mA @ 24V
- Expected Contact Life: 300 kHz (resistive), 100 kHz (inductive)
- Module Keying: Electronic, software configurable
- Outputs: 16 Normally Open (N.O.) individually isolated
- Scheduled Outputs: Synchronization within 16.7 s max, reference to the coordinated system time
- Power Dissipation: Maximum of 4.5 W @ 60 °C (140 °F)
- Isolation Voltage: 250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output
- Wire Category: Category 1
- Short-Circuit Protection: Not available
- Pilot Duty: C300, R150
- Initial Contact Resistance: Maximum of 100 mΩ @ 6V, 1 A
- Switching Frequency: Maximum of 1 operation/3 s (0.3 Hz at rated load)
- Fault Mode States: Hold last state, On or Off (default Off)
- Program Mode States: Hold last state, On or Off (default Off)
Mechanical Specifications
- Slot Width: 1
- RTB Keying: User-defined mechanical
- Shock Resistance: Operating: 30 G, Non-operating: 50 G
- Vibration Resistance: 2 G @ 10...500 Hz
Environmental Specifications
- Maximum Surrounding Air Temperature: 60 °C
- North American Temperature Code: T4A
- Emissions Standard: IEC 61000-6-4
- ESD Immunity: 6 kV contact discharges, 8 kV air discharges
- Relative Humidity: 5...95% non-condensing
- Conducted RF Immunity: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
- EFT/B Immunity: ±4 kV at 5 kHz on signal ports
- Operating Temperature: 0 to 60 °C
- Surge Transient Immunity: ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
- Non-operating Temperature: -40 °C
- Oscillatory Surge Withstand: IEEE C37.90.1: 3kV
Output Specifications
- Off-State Leakage Current Per Point: Maximum of 1.5 mA
- Load Current Per Point: Minimum of 10 mA
- Output Delay Time: OFF to ON: 10 ms max, ON to OFF: 10 ms max
Input Specifications
- Operating Voltage: 5...125V DC, 10...240V AC
-
Voltage and Current Ratings:
- 1 A @ 5...30V DC
- 0.5 A @ 48V DC
- 0.22 A @ 125V DC
- 1.5 A @ 120V AC, 50/60 Hz
- 0.75 A @ 240V AC, 50/60 Hz
Construction
- Enclosure Type: None (open-style)
Technical Specifications - 1756-OW16I
Attribute: 1756-OW16I
Outputs: 16 N.O. individually isolated
Pilot Duty: C300/R150
Operating Voltage Range:
- 5…125V DC
- 10…240V AC
Output Voltage Range (Load Dependent):
- 1 A @ 5…30V DC
- 0.5 A @ 48V DC
- 0.22 A @ 125V DC
- 1.5 A @ 120V AC 50/60 Hz
- 0.75 A @ 240V AC 50/60 Hz
Output Delay Time:
- Off to On: 10 ms max
- On to Off: 10 ms max
Current Draw:
- @ 5.1V: 150 mA
- @ 24V: 150 mA
Total Backplane Power: 4.4 W
Power Dissipation, Max: 4.5 W @ 60 °C (140 °F)
Thermal Dissipation: 15.35 BTU/hr
Off-State Leakage Current Per Point, Max: 1.5 mA per point
Minimum Load Current: 10 mA per point
Initial Contact Resistance, Max: 100 mΩ @ 6V, 1 A