21505-12-40-10-02 Bently Nevada 8 mm Proximity Probe

In stock
Manufacturer:
Bently Nevada
Product No.:
21505-12-40-10-02
Condition:
In Stock
Product Type:
8 mm Proximity Probe
Product Origin:
USA
Weight:
323g
Shipping port:
Xiamen
Warranty:
12 months

UBEST – Trusted Global Automation Parts Supplier

We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.

About Us | Contact

Bently Nevada 7200 Proximity Transducer: Heavy-Duty Vibration Monitoring

Industrial-grade 8mm probe with stainless steel armor for corrosive environments. Features chemical-resistant construction and precise 0-10kHz frequency response for critical machinery protection.

TECHNICAL SPECIFICATIONS

  • Brand: Bently Nevada
  • Model: 21505-12-40-10-02
  • Series: 7200 Proximity Transducer
  • Thread Size: 3/8-24 UNF
  • Cable Length: 1.0m ±0.25m
  • Calibrated Range: 2.0mm (80 mils)
  • Scale Factor: 7.87 V/mm ±9.5%
  • Temp Range: -34°C to +177°C (probe)
  • Corrosion Resistance: H₂SO₄, NH₄OH, MEK
  • Armor: Stainless steel

PART NUMBER DECODER

21505 → Base Model
12 → Unthreaded Length: 120mm
40 → Case Length: 4.0 inches
10 → Cable Length: 1.0m
02 → Connector: Miniature Coaxial

MODEL COMPARISON

Model Key Differences
21505-00-72-10-02 72mm case length
21505-04-48-10-02 48mm case length
21505-22-55-10-02 220mm unthreaded length

PERFORMANCE DATA

Parameter Value Condition
Linearity Error ±0.02mm System calibrated
Temp Sensitivity -3% @65°C/1.27mm gap
Humidity Limit 95% RH Non-condensing

INSTALLATION GUIDE

• Gap setting: 0.25-2.0mm optimal range
• Avoid condensation in humid environments
• Use 3/8-24 UNF mounting threads
• Max cable bend: 25mm radius

PACKAGE CONTENTS

• Proximity probe unit
• Connector protector

SHIPPING

• FedEx/UPS/DHL Express
• International hazardous: Not classified

FREQUENTLY ASKED QUESTIONS

Q: Is this compatible with sulfuric acid?
A: Yes - resistant to 10% concentration

Q: Minimum shaft diameter?
A: 8.9mm (0.35") for reliable measurement

Q: Cable replacement procedure?
A: Must replace entire probe assembly

Q: Difference between 7200 and 3300 series?
A: 7200 has thicker armor for harsh environments