3300/12-02-20-00 Bently Nevada Power Supply Module
UBEST – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Input Voltage Options
95-125 Vac, 50/60 Hz (1.0 A maximum)
190-250 Vac, 50/60 Hz (0.5 A maximum)
Surge Protection
26 A peak or 12 A rms for one cycle during power-up.
Transducer Power
User-programmable -24 Vdc (±2.5%) or -18 Vdc (±2%) for individual transducer voltages.
OK Relay Location
Behind the Power Supply, at the Power Supply Input Module.
Environmental Limits
Operating Temperature: 0°C to +65°C (+32°F to +150°F)
Storage Temperature: -40°C to +85°C (-40°F to +185°F)
Relative Humidity: Up to 95%, noncondensing.
Certifications
CSA/NRTL/C Class I, Div 2 (Groups A, B, C, D)
ATEX II 3 G EEx nC[L] IIC T4 (when installed per document number 132577-01)