6EP1336-2BA10 Siemens Power Supply
Manufacturer:
Siemens
Product No.:
6EP1336-2BA10
Condition:
In Stock
Product Type:
Power Supply
Product Origin:
DE
Weight:
2400g
Shipping port:
Xiamen
Warranty:
12 months
UBEST – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Technical Specifications
| Parameter | Specification |
|---|---|
| Input | 1-phase AC |
| Supply Voltage | ● 1 at AC Rated value 120 V ● 2 at AC Rated value 230 V ● Note Automatic range selection |
| Input Voltage | ● 1 at AC 85 ... 132 V ● 2 at AC 176 ... 264 V |
| Wide-Range Input | No |
| Overvoltage Resistance | 2.3 × Vin rated, 1.3 ms |
| Mains Buffering at Iout Rated | Min. 20 ms; at Vin = 120/230 V |
| Rated Line Frequency | ● 1 50 Hz ● 2 60 Hz ● Rated line range 47 ... 63 Hz |
| Input Current | ● at rated input voltage 120 V 7.5 A ● at rated input voltage 230 V 3.5 A |
| Switch-On Current Limiting (+25 °C) | Max. 11 A |
| Output | Controlled, isolated DC voltage |
| Rated Voltage Vout DC | 24 V |
| Total Tolerance, Static | ± 3 % |
| Static Mains Compensation | Approx. 0.5 % |
| Static Load Balancing | Approx. 1 % |
| Residual Ripple Peak-Peak, Max. | 150 mV |
| Spikes Peak-Peak, Max. (Bandwidth: 20 MHz) | 240 mV |
| Adjustment Range | 24 ... 28 V |
| Output Voltage Adjustable | Yes |
| Output Voltage Setting | Via potentiometer; max. 480 W |
| Status Display | Green LED for 24 V OK |
| Signaling | Relay contact (NO contact, rating 50 V DC/0.3 A) for "24 V OK" |
| On/Off Behavior | No overshoot of Vout (soft start) |
| Startup Delay, Max. | 1.5 s |
| Voltage Rise, Typ. | 50 ms |
| Voltage Increase Time of the Output Voltage | Maximum 500 ms |
| Rated Current Value Iout Rated | 20 A |
| Current Range | 0 ... 20 A ● Note 24 A up to +45°C; +60 ... +70 °C: Derating 5%/K |
| Supplied Active Power | Typical 480 W |
| Short-Term Overload Current | ● On short-circuiting during the start-up typical 35 A ● At short-circuit during operation typical 35 A |
| Duration of Overloading Capability for Excess Current | ● On short-circuiting during the start-up 100 ms ● At short-circuit during operation 100 ms |
| Parallel Switching for Enhanced Performance | Yes |
| Numbers of Parallel Switchable Units for Enhanced Performance | 2 |
| Efficiency | Approx. 90 % at Vout rated, Iout rated |
| Power Loss at Vout Rated, Iout Rated | Approx. 53 W |
| Closed-Loop Control | Dynamic mains compensation (Vin rated ±15 %), max. 1 % Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. 3 % Setting time maximum 10 ms |
| Operating Data | Ambient temperature ● During operation 0 ... 70 °C — Note with natural convection ● During transport -40 ... +85 °C ● During storage -40 ... +85 °C Humidity class according to EN 60721 Climate class 3K3, no condensation |
| Mechanics | Connection technology screw-type terminals Width of the enclosure 115 mm Height of the enclosure 145 mm Depth of the enclosure 150 mm Required spacing ● Top 50 mm ● Bottom 50 mm ● Left 0 mm ● Right 0 mm Weight, approx. 2.4 kg |