8C-PDODA1 Honeywell 51454472-175 Digital Output Module

In stock
Manufacturer:
Honeywell
Product No.:
8C-PDODA1
Condition:
In Stock
Product Type:
Digital Output Module
Product Origin:
USA
Weight:
300g
Shipping port:
Xiamen
Warranty:
12 months

UBEST – Trusted Global Automation Parts Supplier

We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.

About Us | Contact

Function

The 8C-PDODA1 Digital Output bussed 24VDC (DO24V) module switches reliable 24V digital output signals to control process equipment, solenoid valves, and interposing relays.

Notable Features

  • Extensive internal diagnostics for data integrity
  • Optional redundancy
  • Safe-state (FAILOPT) behaviors
  • Direct/Reverse output support
  • Latched, pulsed, or pulse-width modulated output (per channel)
  • Galvanic isolation

Bussed 24VDC DO

The Digital Output Bussed 24VDC supports both internal and external field power excitation. All outputs share a common return (ground). Outputs are powered from either the system supply or an externally connected 24V source, with galvanic isolation available for outputs from external sources.

Safe-state Behavior (FAILOPT)

The Series 8 DO module supports the FAILOPT parameter per channel, allowing outputs to either hold the last value or shed to a safe value defined by the user.

Detailed Specification – Digital Output 24VDC (8C-PDODA1)

Parameter Specification
Input / Output Module 8C-PDODA1 Digital Output 24 VDC, Field Isolated, Bussed output, Coated
IOTA Modules

8C-TDODA1 Non Redundant, Coated 9”;

8C-TDODB1 Redundant, Coated 12”

Output Channels 32
Output Type Source
Voltage Rating 24 VDC
Module current rating 105 mA
Load Voltage 30 VDC Maximum
Load Current 100 mA per channel (Max) and 3.2A per module (Max)
Galvanic Isolation 1000 VAC RMS or ±1500 VDC
On-State Voltage 24 VDC (typ) (load current @ 0.1A max)
Off-State Leak Current 5 µA (max)
Turn-On/Turn-Off Time 10 ms (max)
Gap (0 current) of Output to Field on Switchover None (0ms) (applies to Redundancy only)
Module Removal and Insertion Under Power Supported