Description

The Model AAP135-S00 Pulse Input Module offers 8 isolated channels designed to receive contact ON/OFF, voltage pulse, and current pulse signals. It ensures isolation between the field and the system as well as between each channel, making it suitable for dual-redundant configurations. The module is capable of handling input frequencies ranging from 0 to 10 kHz and supports various input signal types. It provides flexibility in signal processing and is suitable for diverse industrial applications.

Specifications

Items Specifications
Model AAP135-S00
Number of Input Channels 8, isolated channels
Input Signal - 2-wire type: Contact ON/OFF, voltage pulse, current pulse (possible to supply transmitter power supply)
- 3-wire type: Power-supply-type voltage pulse
Input Frequency 0 to 10 kHz
Withstanding Voltage - Between input and system: 500 V AC, for 1 minute
- Between channels: 500 V AC, for 1 minute (*1)
Minimum Input Pulse Width 40 µs
Input Signal Level - Contact input: Open/close levels of relay contact and transistor contact
- Open: 100 kΩ or larger, Close: 200 Ω or less
Contact Capacity - When supplying 12 V DC: 15 V DC 15 mA or higher
- When supplying 24 V DC: 30 V DC 30 mA or higher
Voltage/Current Pulse Input - VH (high level): 3 to 24 V DC
- VL (low level): -1 to 8 V DC
- VH-VL (swing value): 3 V or higher
- Signal source resistance: 1 kΩ or less
- Shunt resistance: Can be selected from none/200/500/1000 Ω. (Open when power is OFF and for the standby side in a dual-redundant configuration)
- Pull-up resistance: 68 kΩ (12 V DC or 24 V DC)
Filter Filter for eliminating chattering can be set. (*2)
Data Update Period 2 ms
Transmitter Power Supply Can select 24 V DC/12 V DC
Limiter Value - 12 V DC ±10 %: 40 mA
- 24 V DC ±10 %: 30 mA
Maximum Current Consumption 300 mA (5 V DC), 400 mA (24 V DC)
Weight 0.3 kg
Dimension 130mm x 107.5mm x 32.8mm
External Connection Pressure clamp terminal, KS cable, MIL connector cable

Suffix Codes

  • -S: Standard type
  • 5: With no explosion protection
  • E: With explosion protection
  • 0: Basic type
  • 3: With ISA Standard G3 option and temperature (-20 to 70 °C) option

Option Codes

  • /13A00: With KS Cable Interface Adapter [Model: ATI3A-00]
  • /K4A00: With KS Cable Interface Adapter [Model: ATK4A-00]
  • /13S00: With Pressure Clamp Terminal Block for Pulse [Model: ATI3S-00]
  • /13S10: With Pressure Clamp Terminal Block for Pulse (surge absorber) [Model: ATI3S-10]
  • /13D00: With Dual Pressure Clamp Terminal Block for Pulse [Model: ATI3D-00]
  • /13D10: With Dual Pressure Clamp Terminal Block for Pulse (surge absorber) [Model: ATI3D-10]