AO810 Analog Output Module

Description

The AO810 Analog Output Module features 8 unipolar analog output channels. To supervise the communication to the D/A converters, the serial data is read back and verified. The open-circuit diagnostic is received during the readback.

The module performs self-diagnostic cyclically. The module diagnostics include process power supply supervision, reported when the supply voltage to output circuitry is too low. This error is reported as a channel error. The channel diagnostic includes fault detection of the channel (only reported on active channels). The error is reported if the output current is less than the output set value and the output set value is greater than 1 mA.

Four different types of MTUs can be used. The TU830 Extended MTU and the TU810 (or TU814) Compact MTU enable wire connection to the devices without additional terminals. The TU812 Compact MTU has a D-Sub 25 pin (male) connector for connection to the process.

Features

  • 8 channels of 0...20 mA, 4...20 mA outputs.
  • OSP sets outputs to predetermined state upon error detection.
  • Analog Output is short circuit secured to ZP or +24 V.

Technical Data

AO810 Analog Output Module Specifications at 25°C

Feature AO810 Analog Output Module
Number of channels 8
Output range 0...20 mA, 4...20 mA (1)
Over range 15%
Output load ≤500 ohms (2), 250 - 850 ohms (3)
Maximum field cable length 600 meters (656 yd.)
Rise time 0 - 90% 0.35 ms RL = 500 ohms
Cycle time ≤2 ms
Error Max. 0.1% at 0 - 500 ohms
Resolution 14 bit
Output Set as Predetermined (OSP) timer 256, 512, 1024 ms
Temperature drift Typ. 30 ppm/°C, Max. 60 ppm/°C
Current consumption 24 V (process power supply, UPx) AO810: 200 mA (max)
Supervision Module: Output power low, Channel: Open-circuit (for current > 1 mA)
Current consumption 5 V (Modulebus) 70 mA (max)
Power dissipation (5) 2.3 W
Isolation Groupwise isolated from ground
Mounting termination units TU810, TU812, TU814, and TU830
MTU keying code AE
Rated insulation voltage 50 V