ABB

ABB AO815 3BSE052605R1 S800 Analog Output Module

In stock
Manufacturer:
ABB
Product No.:
AO815
Condition:
In Stock
Product Type:
Analog Output Module
Product Origin:
Switzerland
Weight:
250g
Shipping port:
Xiamen
Warranty:
12 months

UBEST – Trusted Global Automation Parts Supplier

We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.

About Us | Contact

AO815 3BSE052605R1 Analog Output Module

Description

The AO815 Analog Output Module features 8 unipolar analog output channels. The module performs self-diagnostic cyclically.

Features

  • 8 channels of 4...20 mA outputs.
  • OSP sets outputs to predetermined state upon error detection.
  • 1 group of 8 channels isolated from ground.
  • Analog Output is short circuit secured to ZP or +24 V.
  • 12-bit resolution.
  • HART pass-through communication.

Module diagnostics include:

  • External Channel Error: Reported (only on active channels) if the process power supply voltage to output circuitry is too low or the output current is less than the output set value and the output set value is greater than 1 mA (open circuit).
  • Internal Channel Error: Reported if the output circuit cannot provide the correct current value.
  • Module Error: Reported in case of Output Transistor Error, Short Circuit, Checksum Error, Internal Power Supply Error, or Watchdog error.

The module supports HART pass-through functionality with point-to-point communication. The output filter must be enabled on channels used for HART communication. Shielded field cables are required for process connections if HART is used.

Four different types of MTUs can be used: TU830 Extended MTU and TU810 (or TU814) Compact MTU for wire connection without additional terminals, and TU812 Compact MTU with a D-Sub 25 pin (male) connector for process connection.

Technical Data

AO815 Analog Output Module Specifications at 25°C

Feature AO815 Analog Output Module
Number of channels 8
Output range 4...20 mA
Over range ±15%
Output load Max 750 ohms
Maximum field cable length 600 meters (656 yd.)
Rise time output filter

- disable: 23 ms (0-90%)

- enable: max 4 mA / 12.5 ms

Cycle time 10 ms
Error Max. 0.1%
Resolution 12 bit
Output Set as Predetermined (OSP) timer 256, 512, 1024 ms
Temperature drift Max. 50 ppm/°C
Current consumption 24 V (process power supply, UPx) 165 mA (max)
Current consumption 5 V (Modulebus) 125 mA (max)
Power dissipation (1) 3.5 W
Isolation Groupwise isolated from ground
Mounting termination units TU810, TU812, TU814, TU830, and TU833
MTU keying code DB
Rated insulation voltage 50 V
Dielectric test voltage 500 V a.c.