ABB

ABB DP820 3BSE013228R1 Pulse Counter

In stock
Manufacturer:
ABB
Product No.:
DP820
Condition:
In Stock
Product Type:
Pulse counter
Product Origin:
Switzerland
Weight:
150g
Shipping port:
Xiamen
Warranty:
12 months

UBEST – Trusted Global Automation Parts Supplier

We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.

About Us | Contact

DP820 Incremental Pulse Counter Module

Features

  • Number of Channels: Two channels.
  • Transducer Signal Levels: RS422, 5 V, 12 V, 24 V, and 13 mA interfaces.
  • Simultaneous Measurement: Pulse count and frequency measurement.
  • Pulse Count: Bidirectional 29-bit counter for length/position measurement.
  • Frequency Measurement: Range from 0.25 Hz to 1.5 MHz.

Description

The DP820 is a two-channel pulse counting module designed for incremental pulse transmitters with a frequency range of up to 1.5 MHz. Each channel includes counters and registers for position/length and speed/frequency measurement. It provides balanced inputs for connecting pulse transmitters, along with digital input and output options.

Signal Compatibility

Pulse transmitters with RS422, +5 V, +12 V, +24 V, and 13 mA interfaces can be connected to the DP820 module.

Technical Specifications

  • Power Supply Voltage: 24 V d.c. (12 to 32 V d.c.)
  • Max Non-destructive Voltage on Inputs: 30 V d.c.
  • Maximum Field Cable Length: 200 m
  • Cable Type: Shielded, twisted pair with a characteristic impedance of 100 ohms.
  • Input Filters: Configurable for different pulse encodings and pulse widths.

Input Impedance and Voltage Range

  • Impedance: 100 Ω characteristic impedance for A, B, and ST inputs.
  • Voltage Range:
    • Input A, B, ST:
      • RS422/+5 V /13 mA Range: 2.5 V to 30 V
      • 12 V Range: -30 V to 1.0 V (External resistance)
      • 24 V Range: -30 V to 5.0 V
    • Input DI: 15 V to 30 V

Digital Output

  • Max Load Current: 0.5 A
  • Max Short Circuit Current: 2.4 A
  • Max Leakage Current: 10 μA
  • Max Output Impedance: 0.4 Ω

Measurement Accuracy

  • Max Frequency Measurement Error: Relative error and absolute error included temperature drift.
  • Resolution: Dependent on measuring time, with higher resolutions achieved with longer measuring times.

Power Consumption and Dissipation

  • Current Consumption: 120 mA at 5 V (Modulebus)
  • Power Dissipation: 2.5 W

Other Specifications

  • OSP Timer: 256, 512, 1024 ms
  • Process Voltage Supervision: 2 channels (1 per group)
  • Isolation: Individually isolated channels
  • MTU Compatibility: TU810, TU812, TU814, TU830, or TU833
  • Rated Insulation Voltage: 50 V
  • Dielectric Test Voltage: 500 V a.c.

Dimensions

  • Width: 45 mm (1.77”)
  • Depth: 102 mm (4.01”), 111 mm (4.37”) including connector
  • Height: 119 mm (4.7”)