ABB DP820 3BSE013228R1 Pulse Counter
Manufacturer:
ABB
Product No.:
DP820
Condition:
In Stock
Product Type:
Pulse counter
Product Origin:
Switzerland
Weight:
150g
Shipping port:
Xiamen
Warranty:
12 months
UBEST – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
DP820 Incremental Pulse Counter Module
Features
- Number of Channels: Two channels.
- Transducer Signal Levels: RS422, 5 V, 12 V, 24 V, and 13 mA interfaces.
- Simultaneous Measurement: Pulse count and frequency measurement.
- Pulse Count: Bidirectional 29-bit counter for length/position measurement.
- Frequency Measurement: Range from 0.25 Hz to 1.5 MHz.
Description
The DP820 is a two-channel pulse counting module designed for incremental pulse transmitters with a frequency range of up to 1.5 MHz. Each channel includes counters and registers for position/length and speed/frequency measurement. It provides balanced inputs for connecting pulse transmitters, along with digital input and output options.
Signal Compatibility
Pulse transmitters with RS422, +5 V, +12 V, +24 V, and 13 mA interfaces can be connected to the DP820 module.
Technical Specifications
- Power Supply Voltage: 24 V d.c. (12 to 32 V d.c.)
- Max Non-destructive Voltage on Inputs: 30 V d.c.
- Maximum Field Cable Length: 200 m
- Cable Type: Shielded, twisted pair with a characteristic impedance of 100 ohms.
- Input Filters: Configurable for different pulse encodings and pulse widths.
Input Impedance and Voltage Range
- Impedance: 100 Ω characteristic impedance for A, B, and ST inputs.
-
Voltage Range:
-
Input A, B, ST:
- RS422/+5 V /13 mA Range: 2.5 V to 30 V
- 12 V Range: -30 V to 1.0 V (External resistance)
- 24 V Range: -30 V to 5.0 V
- Input DI: 15 V to 30 V
-
Input A, B, ST:
Digital Output
- Max Load Current: 0.5 A
- Max Short Circuit Current: 2.4 A
- Max Leakage Current: 10 μA
- Max Output Impedance: 0.4 Ω
Measurement Accuracy
- Max Frequency Measurement Error: Relative error and absolute error included temperature drift.
- Resolution: Dependent on measuring time, with higher resolutions achieved with longer measuring times.
Power Consumption and Dissipation
- Current Consumption: 120 mA at 5 V (Modulebus)
- Power Dissipation: 2.5 W
Other Specifications
- OSP Timer: 256, 512, 1024 ms
- Process Voltage Supervision: 2 channels (1 per group)
- Isolation: Individually isolated channels
- MTU Compatibility: TU810, TU812, TU814, TU830, or TU833
- Rated Insulation Voltage: 50 V
- Dielectric Test Voltage: 500 V a.c.
Dimensions
- Width: 45 mm (1.77”)
- Depth: 102 mm (4.01”), 111 mm (4.37”) including connector
- Height: 119 mm (4.7”)