ABB SPAE010 | High Impedance Protection Relay SPAE 010
Manufacturer:
ABB
Product No.:
SPAE010
Condition:
In Stock
Product Type:
High Impedance Protection Relay
Product Origin:
DE
Weight:
2000g
Shipping port:
Xiamen
Warranty:
12 months
UBEST – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
| ABB SPAE010 High Impedance Protection Relay | |
|---|---|
| Energizing Inputs | Terminal numbers: 40-41, 40-42, 40-43 Rated voltage, Un: 50 V, 100 V, 200 V |
| Thermal Withstand Capability | - Continuous: 1.3 x Un - For 1 s: 10 x Un |
| Rated Frequency, fn | 50/60 Hz |
| ABB Protection Characteristics | |
|---|---|
| Voltage Setting Range, U>/Un | 0.4...1.2 x Un |
| Operating Current | 9...27 mA |
| Operating Time | See fig. 5 |
| Drop-off Time | ≤120 ms |
| Drop-off/Pick-up Ratio | 0.8 |
| ABB Output Contact Ratings | |
|---|---|
| Trip Contacts, Terminal Numbers | 65-66, 74-75 |
| Rated Voltage, Make or Break | 250 Vac or dc |
| Make and Carry for 0.5 s | 30 A |
| Make and Carry for 3 s | 15 A |
| Continuous Carry | 5 A |
| Breaking Capacity for DC | 5 A / 3A / 1 A (L/R≤40 ms, at 48/110/220 V dc) |
| Contact Material | Gold plated AgNi |
| Signalling Contacts, Terminal Numbers | 67-68-69, 70-71-72 |
| Rated Voltage, Make or Break | 250 Vac or dc |
| Make and Carry for 0.5 s | 10 A |
| Make and Carry for 3 s | 8 A |
| Continuous Carry | 5 A |
| Breaking Capacity for DC | 1A / 0.25A / 0.15A (L/R≤40 ms, at 48/110/220 V dc) |
| Contact Material | Gold plated AgNi |
| ABB Auxiliary Power Supply | |
|---|---|
| Supply Voltage, SPAE 010 | 80...265 V ac or dc |
| Supply Voltage, SPAE 011 | 18...80 V dc |
| Power Consumption | About 5 W |
| ABB Insulation Tests | |
|---|---|
| Dielectric Test | IEC 60255-5, 2kV, 50Hz, 1min |
| Impulse Voltage Test | IEC 60255-5, 5kV, 1.2/50µs, 0.5J |
| Insulation Resistance Measurement | IEC 60255-5, >100MΩ, 500Vdc |
| ABB Electromagnetic Compatibility Tests | |
|---|---|
| High-frequency (1MHz) Burst Disturbance Test | IEC 60255-22-1 - Common mode: 2.5 kV - Differential mode: 1.0 kV |
| Electrostatic Discharge Test | IEC 60255-22-2 and IEC 61000-4-2 - Contact discharge: 6 kV - Air discharge: 8 kV |
| Fast Transient Disturbance Test | IEC 60255-22-4 and IEC 61000-4-4 - All ports: 2 kV |
| Spark Interference Test Voltage | Inputs and outputs as per SS 436 15 03, PL 4: 4...8 kV |
| ABB Environmental Conditions | |
|---|---|
| Specified Service Temperature Range | -10...+55°C |
| Transport and Storage Temperature Range | -40...+70°C |
| Temperature Influence on Operating Values | Over the specified service temperature range: <0.2%/°C |
| Damp Heat Test, Cyclic | IEC 60068-2-30: +25...55°C, r.h. > 93%, 6 cycles |
| Degree of Protection by Enclosure | When panel mounted: IP 54 |
| Weight of Fully Equipped Relay | 2 kg |