AI880 3BSE028600R1 ABB Analog Input Unit Module
Manufacturer:
ABB
Product No.:
AI880
Condition:
In Stock
Product Type:
Analog Input Module
Product Origin:
Switzerland
Weight:
250g
Shipping port:
Xiamen
Warranty:
12 months
UBEST – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
AI880 High Integrity Analog Input Module
Features
- 8 channels for 0...20 mA, 4...20 mA, single-ended unipolar inputs.
- Single or redundant configuration.
- 1 group of 8 channels isolated from ground.
- 12-bit resolution.
- Loop Supervised DI function.
- Configurable alarm limit for field power outputs.
- Configurable over/under range for current inputs.
- Current limited transmitter supply per channel.
- Advanced on-board diagnostics.
- Certified for SIL3 according to IEC 61508.
- Certified for Category 4 according to EN 954-1.
- Complies with the NAMUR recommendation NE43, and supports configurable over- and under-range limits.
- HART pass-through communication (AI880A).
Technical Data
General Specifications at 25°C
- Number of channels: 8
- Type of input: Unipolar single-ended
-
Measurement range:
- 0...20 mA
- 4...20 mA
-
Over range:
- +12% (0...20 mA)
- +15% (4...20 mA)
- Input impedance (at current input): 250 Ω (with Shunt stick TY801)
- Maximum field cable length: 600 meters (656 yd.)
- Voltage input, maximum non-destructive: 11 V d.c.
- NMRR, 50 Hz, 60 Hz: >40 dB
- Error: <0.1%
- Safety accuracy: 1.9% (configurable 0.6-5%)
- Resolution: 12-bit
- Temperature drift: Max. 50 ppm/°C
- Update cycle time: 10 ms
-
Current consumption:
- 24 V (Modulebus): 50 mA (max)
- 5 V (Modulebus): 45 mA
- 24 V (process power supply, UPx): 260 mA (max) (4 + transmitter current)
- Power dissipation: 2.4 W
Transmitter Supply (per channel)
-
HART Compatible:
- Voltage: Process power supply (Upx) - max 4.5 V
- Current: 32 mA ± 10%
Voltage Supervision
- Internal voltage, field power input, field power output per channel
Input Filter Rise Time (0-90%)
- 190 ms (HW filter)
Isolation
- 8 inputs isolated from ground in one group
Module Termination Units
- TU834 (single)
- TU844, TU845, TU854 (redundant)
MTU Keying Code
- FF (AI880)
Rated Insulation Voltage
- 50 V
Dielectric Test Voltage
- 500 V a.c.