CC-PAIL51 Analog Input Module - Honeywell

In stock
Manufacturer:
Honeywell
Product No.:
CC-PAIL51
Condition:
In Stock
Product Type:
Analog Input Module
Product Origin:
USA
Weight:
350g
Shipping port:
Xiamen
Warranty:
12 months

UBEST – Trusted Global Automation Parts Supplier

We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.

About Us | Contact

Low Level Analog (Temperature) Input – CC-PAIL51

Function: The Low Level IOP module supports up to 16 channels of temperature inputs, with each channel configurable for either Thermocouple (TC) or Resistance Temperature Device (RTD) inputs. Unlike the LLMUX (CC-PAIM01), this module supports 16 channels directly on the Series-C IOTA, eliminating the need for an external Process Manager FTA.

Notable Features:

  • TC and RTD Operation: Each channel can be configured for either thermocouple or RTD inputs.
  • Cold Junction Compensation: Ensures accurate temperature readings.
  • 1 Second PV Scanning: Provides up-to-date temperature readings every second.
  • OTD Protection: Offers configurable Open Thermocouple Detection protection.

Detailed Specifications:

Input / Output Model:

  • Model: CC-PAIL51
  • IOTA (16pt) Model: CC-TAIL51 9”

Input Type:

  • Thermocouple or RTD: Configurable per channel

Temperature:

  • Operating Temperature: -40 to +70 ℃
  • Storage Temperature: -40 to +85 ℃

Input Channels:

  • Isolation: Fully isolated Channel to Channel and Channel to Power System
  • Scan Rate: 1 Second
  • Channel Bandwidth: 0 to 4.7 Hz (-3 dB)

Nominal Input Range (TC only):

  • Range: -20 to +100 millivolts

Maximum Normal Mode Continuous Input:

  • Thermocouple: -10 to +10 volts
  • RTD: -1 to +2 Volts @ 100 milliamps

Accuracy and Stability:

  • Gain Error: 0.050% full scale max
  • Temperature Stability (TC, Millivolt inputs): +/-20 ppm per max
  • RTD Inputs: +/-20 ppm per max
  • Long Term Drift: 500 ppm

Input Impedance (TC only):

  • Impedance: 1 megohm at dc

Common Mode Voltage (CMV):

  • Respect to Power System common, dc to 60 Hz: +/-250 VDC or VAC RMS

Common Mode Rejection Ratio (CMRR):

  • 50 or 60 Hz (with 1000 ohms source impedance max.): 120 dB min

Channel Isolation:

  • Voltage, Channel-to-Channel, dc to 60 Hz: +/-250 VDC or VAC RMS

Crosstalk:

  • dc to 60 Hz: 80 dB (120 dB at 50 and 60 Hz)

Noise Rejection:

  • NMRR at 50/60 Hz: 60 dB min

Line Frequency Integration:

  • Selection: Fixed selection of 50 Hz or 60 Hz

RTD Sensor Excitation Current:

  • Current: 1 milliamp

Cold Junction Compensation:

  • Range: -20 to +60 ℃ (+/-0.5 ℃ typical)

TC Linearization Accuracy:

  • Accuracy: ± 0.05 Ω / ℃

Open Thermocouple Detection (OTD):

  • Detection: Each conversion qualified, ≤ 1000 Ω = guaranteed no-trip, ≥ 1500 Ω guaranteed trip.

RTD Max Lead Resistance:

  • Resistance: 15 Ω

Supported RTD Types:

  • Pt: 100 ohm DIN 4376: -180 to +800 ℃
  • Pt: 100 ohm JIS C-1604: -180 to +650 ℃
  • Ni: 120 ohm ED #7: -45 to +315 ℃
  • Cu: 10 ohm SEER: -20 to +250 ℃
  • Cu: 50 ohm SEER: -50 to +150 ℃

Supported Thermocouple Types:

  • ANSI specification J: -200 to +1200 ℃
  • ANSI specification K: -100 to +1370 ℃
  • ANSI specification E: -200 to +1000 ℃
  • ANSI specification T: -230 to +400 ℃
  • ANSI specification B: +100 to +1820 ℃
  • ANSI specification S: 0 to +1700 ℃
  • ANSI specification R: 0 to +1700 ℃

Supported Millivolt Types:

  • Range: -20 to +100 millivolts

Weight:

  • Module Weight: 0.35 kg