CI854AK01 3BSE030220R1 ABB PROFIBUS-DP/V1 Interface Module
Manufacturer:
ABB
Product No.:
CI854AK01
Condition:
In Stock
Product Type:
Interface Module
Product Origin:
USA
Weight:
700g
Shipping port:
Xiamen
Warranty:
12 months
UBEST – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Description
The CI854A/TP854 connects PROFIBUS DP to AC 800M controllers. PROFIBUS DP slave devices, such as the remote I/Os S800 and S900, can be connected directly. PROFIBUS PA slave devices can be connected via the PROFIBUS linking device LD 800P.
PROFIBUS DP Interface Key Features
- Redundant Line Interface: PROFIBUS DP with two DB9 female connectors located on the TP854 Baseplate.
- Mounting: Simple DIN-rail mounting.
- Data Transfer: Supports both cyclic and acyclic DP communication, along with slave redundancy.
- Connection Capacity: Use of repeaters allows a maximum of 124 nodes to be connected on one PROFIBUS DP network; up to 32 nodes permitted per segment.
- Alpha Code Locking: Pre-set, two-letter alpha code locking device installed in unit base prevents mounting of incompatible components.
- Transmission Speed: Selectable between 9.6 kbit/s and 12 Mbit/s.
- Master Redundancy: Support of PROFIBUS DP master redundancy (CI854A only).
- Hot Swap Support: Supported by CI854A.
LED Indicators and Functions
- F(ault) / Red: Indicates a unit error, set during controller reset and managed by the control software post-reset.
- R(un) / Green: Signifies normal operation, reset by hardware during controller reset and managed by the control software post-reset.
- RxA / Yellow and RxB / Yellow: Indicates data reception on Line A and Line B. Each telegram received causes the LED to flash; appears static in normal operation.
- PRIM(ary) / Yellow (CI854A): This LED is on in both single and redundant configurations, indicating the primary CI854A in redundant setups.
- DUAL / Yellow (CI854A): On when CI854A is operating in a redundant configuration.
Technical Specifications
- Galvanic Isolation: Yes
- Status Indicators: Green (normal), Red (fault), Yellow (data traffic, primary configuration, redundancy)
- Connectors: Two DB9, female on TP854
- Current Consumption: 190 mA typical, maximum 240 mA from CEX-Bus 24 V DC
- Power Dissipation: 4.6 W typical
- Capacity: Max 32 nodes on PROFIBUS without repeater
- Protection Rating: IP20 according to EN60529, IEC 529
- Weight: 700 g (1.5 lb) for package CI854K01 and CI854AK01
- Dimensions: W 59 x H 185 x D 127.5 mm (W 2.9 x H 7.3 x D 5.0 in)