DI830 Digital Input Module

Description

The DI830 is a 16-channel digital input module designed for 24 V d.c. inputs with current sinking within the S800 I/O system. It operates within an input voltage range of 18 to 30 V d.c., with an input current of 6 mA at 24 V d.c.

Eight types of MTUs can be used with the DI830, including extended and compact MTUs offering various connection options and features.

Event Recording The DI830 module supports event recording (SOE) functionality, announcing signal changes at digital input channels with a time stamp. Events are generated on both positive and negative edges of the signal, with a time stamp resolution of 0.4 milliseconds.

Features

  • 16 channels for 24 V d.c. inputs with current sinking.
  • 2 isolated groups of 8 channels with voltage supervision.
  • Input status indicators.
  • Sequence of event (SOE) functionality.
  • Shutter filter.

Technical Data

DI830 Digital Input Module Specifications

Feature DI830 Digital Input Module
Number of channels 16 (2 x 8), current sinking
Rated voltage (Process power supply range) 24 V d.c. (18 to 30 V d.c.)
Input voltage range, “1” 13 to 30 V
Input voltage range, “0” -30 to +5 V
Nominal input channel current 7.4 mA @ 24 V d.c.
Input Current, “1” >4.0 mA
Input Current, “0” <2.0 mA
Input impedance 3.2 kΩ
Maximum field cable length 600 m (656 yd.)
Filter times (digital, selectable) 0 to 100 ms
Shutter filter

Shutter period: 0 to 255 s

Shutter trigger: 0 to 255 changes

Recovery time: 0 to 65535 s

Event recording resolution 0.4 ms
Event recording accuracy -0.3 ms to +0.7 ms
Process voltage supervision 2 channels (1 per group)
Current consumption 5 V (Modulebus)

Max: 120 mA

Typ: 100 mA

Power dissipation 2.3 W
Isolation Yes, opto
Mounting termination units TU810, TU812, TU814, TU818, TU830, TU833, TU838 or TU850
MTU keying code AA
Rated insulation voltage 50 V
Dielectric test voltage 500 V a.c.