F2DO1602 | HIMA HIMatrix F2 DO 16 02 Safety-Related Remote I/O Module
UBEST – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
The HIMA F2 DO 16 02 is a compact safety-related remote I/O system housed in a metal enclosure, featuring 16 safety-related relay outputs. It is designed for integration with HIMax or HIMatrix controllers via safeethernet, expanding the I/O capabilities without executing user programs independently.
Key Features:
- 16 Safety-Related Relay Outputs: Provides reliable control in safety-critical applications.
- Certifications: TÜV certified for safety-related applications up to SIL 3 (IEC 61508, IEC 61511, IEC 62061), Cat. 4, and PL e (EN ISO 13849-1), as well as SIL 4 (EN 50126, EN 50128, EN 50129).
- Safety Functionality: Operates on the de-energize to trip principle, ensuring safe operation during system faults or channel failures. Fault conditions are indicated by a FAULT LED and can trigger user-programmed reactions.
- Energized to Trip Applications: Capable of energized to trip functionality for specific safety functions.
Technical Specifications:
- Output Type: Relay outputs supporting up to 30 VAC/60 VDC.
- Operating Temperature: 0°C to +60°C.
- Mounting: Suitable for Ex-zone 2 installations (refer to Chapter 4.1.3).
-
Programming Tools Compatibility:
- ELOP II Factory: Variant designed for use with the ELOP II Factory programming tool.
- SILworX: Variant compatible with the SILworX programming tool.
Safety and Application:
The HIMA F2 DO 16 02 remote I/O module is crucial for extending the I/O capabilities of safety systems in various industries, including process control, discrete manufacturing, rail signaling, and more. It adheres to stringent safety standards and provides robust performance in demanding environments.