F5-MD1616R Mixed I/O Module – 16 Inputs 16 Outputs Relay 24VDC
-
General Specifications
- Brand: Flexem
- Series: FC5 Digital I/O Module
- Model: F5-MD1616R
- Input Points: 16 digital inputs (bipolar)
- Output Points: 16 relay outputs
- Supply Voltage: 24VDC for internal logic
-
Input Characteristics
- Input Type: Source/sinking (bipolar compatible)
- Rated Voltage: 24VDC (input range 0~28.8VDC)
- Rated Current: 7mA typical at 24VDC
- Maximum Peak Voltage: 30V (limited to 1 hour per day)
- ON State Voltage: >15V (15~28.8VDC range)
- OFF State Voltage: <5V (0~5V range)
- ON State Current: >2.5mA
- OFF State Current: <1.0mA
- Input Impedance: 3.3kΩ
- Isolation: Optocoupler isolation per channel
- Compatibility: Works with 2-wire and 3-wire sensors
- Cable Length: 100m max with shielded cable, 50m unshielded
-
Input Filter Settings
- Default Filter Time: 1ms
- Selectable Range: Unfiltered to 100ms
- Resolution: 16 equally divided levels
- Flexible filtering for noise immunity
-
Relay Output Specifications
- Output Type: Relay (mechanical contacts)
- Rated Voltage: 24VDC or 24VAC (resistive load)
- Voltage Range: 19.2~28.8VDC
- Rated Current: 2A per point (resistive)
- Maximum Switching Power: 60W or 62.5VA
- Minimum Load: 10mA for reliable contact wetting
- Mechanical Life: 20 million operations
- Electrical Life: 100,000 operations at rated load
- Isolation: 1500VAC between coil and contacts
-
Frequently Asked Questions
-
What is the difference between F5-MD1616R and transistor output modules?
The F5-MD1616R uses relay outputs, which handle both AC and DC loads up to 2A. They provide isolation but have slower switching speeds than transistors. -
Can I use this module with both NPN and PNP sensors?
Yes, the inputs are bipolar and accept both sourcing (PNP) and sinking (NPN) sensors. This makes the F5-MD1616R very flexible. -
What is the maximum switching frequency for relays?
For mechanical relays, we recommend less than 1Hz for full electrical life. For higher frequencies, consider transistor output modules. -
Does this module work with the Flexem FC5 CPU?
Yes, it connects directly to any Flexem FC5 CPU via the expansion bus. The system automatically detects the module. -
Do I need external fuses for outputs?
We recommend external fuses or circuit breakers for each common group to protect against short circuits, as relays do not have built-in protection.
-