F60CPU03 – Central Safety Controller for HIMatrix F60 Systems

Technical Specifications

  • Brand: HIMA
  • Model: F60CPU03 (CPU 03 module for HIMatrix F60)
  • Total Program Memory: 5 MB minus 64 kB for CRC storage
  • Minimum Response Time: ≥ 6 milliseconds
  • Ethernet Interfaces: 4 x RJ-45, 10/100Base-T with integrated switch
  • Fieldbus Interfaces: 2 x 9-pin D-sub (FB1 and FB2 with pluggable submodules)
  • Operating Voltage: 24 VDC, -15% to +20%, with safe isolation per IEC 61131-2
  • Operating Currents: 3.3 VDC at 1.5 A, 5 VDC at 0.1 A
  • Date/Time Buffer: Gold capacitor (no battery replacement needed)
  • Ambient Temperature (Operation): 0°C to +60°C
  • Storage Temperature: -40°C to +85°C
  • Space Requirement: 6 RU, 4 HP (Eurocard format)
  • Weight: 280 grams
  • Safety Certifications: TÜV certified to IEC 61508 up to SIL 3, IEC 61511, EN ISO 13849-1, IEC 62061, EN 50156-1, EN 298, EN 230
  • EMC Compliance: CE mark

Frequently Asked Questions (FAQ)

  • Can the F60CPU03 work with other HIMatrix F60 I/O modules? Yes, it communicates directly with all F60 series I/O modules in the same subrack.
  • What software do I need to program this CPU? Use HIMA's ELOP II Factory or SILworX programming environments.
  • Does the module support hot swapping? No, you must power down the subrack before inserting or removing the F60CPU03.
  • How do I configure the IP address? Use the PADT (Programming and Debugging Tool) via Ethernet connection.
  • What happens if the gold capacitor fails? The date and time settings will reset after a power cycle, but the program memory remains intact.
  • Can I use this module for non-safety applications? Yes, it also runs standard protocols like Modbus TCP and OPC for non-critical tasks.

Technical documentation and support provided by Ubest Automation – your partner for HIMA safety controllers and industrial automation components.

© 2026 Ubest Automation Limited. https://www.ubestplc.com/ All rights reserved.