FC-TSFIRE-1624 Honeywell FTA Field Termination Assembly
Manufacturer:
Honeywell
Product No.:
FC-TSFIRE-1624
Condition:
In Stock
Product Type:
Field Termination Assembly
Product Origin:
USA
Weight:
300g
Shipping port:
Xiamen
Warranty:
12 months
UBEST – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
General Information
| Type numbers | FS-TSFIRE-1624, FC-TSFIRE-1624 |
|---|---|
| Approvals | CE, TUV, UL, CSA, FM |
Power Requirements
| Voltage | 24 V DC +25% / –15% |
|---|---|
| Current | Max. 570 mA (at 24 V DC ext.) With EOL resistors: Typ. 70mA (at 24 V DC ext.) No load: Typ. 11mA (at 24 V DC ext.) |
Input Specifications
| Number of channels | 16 |
|---|---|
| Input Voltage | With EOL resistor (4k7): Typ. 20.5 V DC (at 24 V DC ext.) No load: Typ. 23.5 V DC (at 24 V DC ext.) |
| Channel resistance | 680 Ω ±5% |
| Shorted current | 35 mA (at 24 V DC ext.) |
Relay Specifications
| Relay voltage | 17 – 39 V DC |
|---|---|
| Current | Typ. 8.5 mA at 24 V DC |
| Termination | Screw terminals: - Max. wire diameter: 2.5 mm² (AWG 14) - Strip length: 7 mm (0.28 in) - Tightening torque: 0.5 Nm (0.37 ft-lb) |
Field Termination Assembly Module
| Field wire resistance | < 100 Ω |
|---|---|
| End-of-line (EOL) resistor | For example 4k7, ± 5% (0.25 W) (see F&G Application Manual, PM.MAN.8163) |
| HYDROGEN (Group A & B) | Max. loop inductance: 60 mH Max. loop capacitance: 0.3 µF |
| NON-HYDROGEN (Group C & D) | Max. loop inductance: 230 mH Max. loop capacitance: 7 µF |
Physical Specifications
| Module dimensions | 170 × 70 × 64 mm (L × W × H) 6.72 × 2.76 × 2.52 in (L × W × H) |
|---|---|
| DIN EN rails | TS32 / TS35 × 7.5 |
| Used rail length | 171 mm (6.73 in) |