FSL100-UVIR Honeywell Flame Detector UV/IR 110ft Range
Manufacturer:
Honeywell
Product No.:
FSL100-UVIR
Condition:
In Stock
Product Type:
Flame Detector
Product Origin:
USA
Weight:
465g
Shipping port:
Xiamen
Warranty:
12 months
UBEST – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Honeywell FSL100-UVIR: Multi-Spectrum Flame Detector for Fast Response
- Brand & Model: Honeywell FSL100-UVIR – part of the FSL100 SERIES FLAME DETECTORS.
- Detection Range: 110 ft (35 m) for IR3; 80 ft (25 m) for UV and UV/IR models.
- Cone of Vision: 90° minimum both horizontally and vertically.
- Power Supply: 10-28 VDC (12-24 VDC nominal) for flexible installation.
- Operating Current: 25 mA at 24 VDC during normal operation.
- Alarm Current: ±75 mA at 24 VDC when detecting a fire.
- Startup Time: Less than 10 seconds from power-on.
- Alarm Response Time: Adjustable from 8 to 30 seconds.
- Housing Material: Glass Reinforced Polyester (GRP), UV resistant, V-0 self-extinguishing.
- Ingress Protection: IP65 for outdoor and dusty environments.
- Operating Temperature: –40 ˚F to +158 ˚F (–40 ˚C to +70 ˚C).
- Weight: 1.05 lb (465 g) – lightweight and easy to mount.
Outputs & Connectivity – Honeywell FSL100-UVIR
- 4-20 mA Output (stepped, sinking, non-isolated): 0 mA for power fault, 2 mA for optical fault, 4 mA for normal, >20 mA for alarm.
- Alarm Relay: SPDT, 30 VDC – 2 A, 60 W max. De-energized during normal operation.
- Fault Relay: SPDT, 30 VDC – 2 A, 60 W max. Energized during normal operation.
- Connect to fire control panels using EOL and alarm resistors.
- Connect directly to PLCs with 4–20 mA input cards.
- Use relay outputs for devices like horns, strobes, or shut-off valves.
FAQ – Honeywell FSL100 SERIES FLAME DETECTORS
- Q: What is the difference between FSL100-UV, FSL100-UVIR, and FSL100-IR3? A: UV sees only UV flames; UVIR adds IR for false alarm rejection; IR3 uses three IR sensors for long range (110 ft).
- Q: Can I use the FSL100-UVIR outdoors? A: Yes, IP65 and –40°F to +158°F rating covers outdoor use.
- Q: Does it support non-latching alarm output? A: Yes, you can select non-latching mode via configuration.
- Q: What happens during a self-test failure? A: The yellow LED flashes, and the detector guides you to repeat the test.
Author: Ubest Automation – your partner for industrial fire and gas detection.
© 2026 Ubest Automation Limited. https://www.ubestplc.com/ All rights reserved.
Contact: sales@ubestplc.com | Phone: +86 180 3000 5825 (Click to chat on WhatsApp)