GE

GE Fanuc IC670ALG630 | Isolated Thermocouple Input Module

In stock
Manufacturer:
GE
Product No.:
IC670ALG630
Condition:
In Stock
Product Type:
Isolated Thermocouple Input Module
Product Origin:
USA
Weight:
300g
Shipping port:
Xiamen
Warranty:
12 months

UBEST – Trusted Global Automation Parts Supplier

We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.

About Us | Contact

GE Fanuc IC670ALG630 Thermocouple Input Module - 8-Channel Precision Measurement

The IC670ALG630 delivers high-accuracy temperature monitoring with 8 isolated channels supporting 12 thermocouple types for industrial process control applications.

Key Features

  • Multi-thermocouple support: J, K, T, E, S, R, B, N, G, C, D, Platinel II
  • High precision: ±0.5°F conformity error
  • Excellent noise rejection: 60dB normal mode, 120dB common mode
  • Compact design: Only 0.3kg (9oz) weight
  • Wide voltage spans: 19.5mV to 625mV ranges

Technical Specifications

  • Brand: GE Fanuc
  • Model: IC670ALG630
  • Type: Field Control Thermocouple Input
  • Channels: 8 isolated inputs
  • Resolution: 15 bits + sign
  • Accuracy: ±0.1% reading + ±0.05% span (J/K/T/E types)
  • Current Draw: 195mA max @5VDC
  • Isolation: 250VAC between channels
  • Dimensions: 3"×3"×4" (76×76×102mm)
  • Weight: 0.3kg (9oz)

Measurement Performance

  • Temperature sensitivity: ±0.1% reading + ±1.5µV/°C
  • Common mode voltage: 250Vrms (350VDC peak)
  • Rejection rates: 60dB normal/120dB common mode

Supported Thermocouple Types

  • Standard types: J, K, T, E
  • High-temp types: S, R, B, N
  • Specialty types: G, C, D, Platinel II

Installation & Wiring

  • Field Control baseplate mounting
  • Observe channel isolation limits
  • Use proper thermocouple wire
  • Maintain proper cold junction compensation

Frequently Asked Questions

  • Q: What's the temperature range?
    A: Depends on thermocouple type - up to 1820°C (3308°F) with type B.
  • Q: Is cold junction compensation included?
    A: Yes, built into the module.
  • Q: Can I mix thermocouple types?
    A: Yes, each channel is independently configurable.
  • Q: What's the update rate?
    A: Approximately 50ms per channel.
  • Q: Is special calibration needed?
    A: Factory calibrated, but field verification recommended.

Typical Applications

  • Process temperature monitoring
  • Industrial furnace control
  • Heat treatment systems
  • Power generation monitoring