{"product_id":"hima-himatrix-f60-di-32-01-safety-rated-digital-input-module","title":"HIMA HIMatrix F60 DI 32 01 Safety-Rated Digital input Module","description":"\u003ch3\u003eProduct Description\u003c\/h3\u003e\u003cp\u003e\u003cstrong\u003eHIMA HIMatrix F60 DI 32 01\u003c\/strong\u003e\u003cstrong\u003e(F60DI3201) i\u003c\/strong\u003es a module featuring 32 digital inputs designed for the modular F60 system. It is suitable for safety-related applications, certified by TÜV for up to SIL 3 according to IEC 61508, IEC 61511, IEC 62061, Cat. 4 and PL e according to EN ISO 13849-1, and SIL 4 according to EN 50126, EN 50128, and EN 50129.\u003c\/p\u003e\u003ch3\u003eKey Features:\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003e32 digital inputs\u003c\/li\u003e\n\u003cli\u003eInputs are galvanically separated to the I\/O bus\u003c\/li\u003e\n\u003cli\u003eCan be inserted in the F60 subrack's slots 3 to 8 (slots 1 and 2 reserved for power supply and central modules)\u003c\/li\u003e\n\u003cli\u003eEquipped with safety-related inputs divided into 4 groups of 7 inputs and 1 group of 4 inputs\u003c\/li\u003e\n\u003cli\u003eCapable of line control for detecting short-circuits or open-circuits on emergency stop inputs\u003c\/li\u003e\n\u003cli\u003eError handling includes triggering the ERR LED and processing a low-level signal in the event of a fault\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\u003ch4\u003eGeneral:\u003c\/h4\u003e\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eOperating Voltage:\u003c\/strong\u003e 24 VDC, -15% to +20%, ripple \u0026lt; 15%, from a power supply unit with safe insulation according to IEC 61131-2\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOperating Data:\u003c\/strong\u003e 3.3 VDC \/ 0.05 A, 24 VDC \/ 0.2 A\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAmbient Temperature:\u003c\/strong\u003e 0°C to +60°C\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eStorage Temperature:\u003c\/strong\u003e -40°C to +85°C\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eProtection Class:\u003c\/strong\u003e III (IEC\/EN 61131-2)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePollution Degree:\u003c\/strong\u003e II (IEC\/EN 61131-2)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAltitude:\u003c\/strong\u003e \u0026lt; 2000 m\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHousing:\u003c\/strong\u003e Standard IP20\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSpace Requirement:\u003c\/strong\u003e 6 RU, 4 HP\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWeight:\u003c\/strong\u003e 260 g\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch4\u003eDigital Inputs:\u003c\/h4\u003e\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Voltage:\u003c\/strong\u003e Nominal 24 VDC\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Current:\u003c\/strong\u003e Approximately 7 mA per channel\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Delay:\u003c\/strong\u003e 5 ms\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDebouncing Time:\u003c\/strong\u003e Configurable, typically 0 to 25 ms\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eLine Control:\u003c\/strong\u003e Supports line control for emergency stop applications according to EN ISO 13849-1\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch4\u003eSafety Functions:\u003c\/h4\u003e\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eSafety Standards:\u003c\/strong\u003e IEC 61508 (SIL 3), IEC 61511, IEC 62061, EN ISO 13849-1 (Cat. 4, PL e), EN 50126, EN 50128, EN 50129 (SIL 4)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eFault Detection:\u003c\/strong\u003e Fault detection mechanisms include line control for detecting short-circuits or open-circuits, ERR LED indication, and error code generation for user program handling\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch4\u003eCertification:\u003c\/h4\u003e\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eTÜV Certification:\u003c\/strong\u003e Certified for safety-related applications up to SIL 3 and SIL 4\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConformity Marks:\u003c\/strong\u003e CE, other relevant conformity marks\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch4\u003eEnvironmental Requirements:\u003c\/h4\u003e\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eOperating Temperature:\u003c\/strong\u003e -25°C to +70°C for DI 32 014 variant\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eVibration and Shock:\u003c\/strong\u003e Tested according to EN 50125-3, EN 50155 (class 1B according to IEC 61373)\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch4\u003eStatus Indicators:\u003c\/h4\u003e\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eRUN LED (Green):\u003c\/strong\u003e Indicates operating voltage presence\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eERR LED (Red):\u003c\/strong\u003e Indicates module or external faults\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eI\/O LEDs (Yellow):\u003c\/strong\u003e Indicate the activity status of each channel\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch3\u003eEquipment, Scope of Delivery:\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eDI 32 01:\u003c\/strong\u003e Standard module with 32 digital inputs\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDI 32 014:\u003c\/strong\u003e Enhanced module with extended temperature range, vibration and shock resistance\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch3\u003eConnection and Installation:\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eMounting:\u003c\/strong\u003e In F60 subrack slots 3 to 8\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWiring:\u003c\/strong\u003e Ensure proper connection to avoid cross-circuits, improper connections, and earth faults\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eESD Protection:\u003c\/strong\u003e Follow ESD protective measures to avoid damage\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eFor detailed instructions on installation, configuration, and operation, refer to the relevant sections of the HIMatrix system manuals and safety manuals.\u003c\/p\u003e","brand":"HIMA","offers":[{"title":"Default Title","offer_id":49201663574298,"sku":"F60DI3201","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0873\/6240\/4634\/files\/F60DI3201.jpg?v=1718802158","url":"https:\/\/www.ubestplc.com\/products\/hima-himatrix-f60-di-32-01-safety-rated-digital-input-module","provider":"Ubest Automation Limited","version":"1.0","type":"link"}