Honeywell 8C-PAIHA1 Analog Input with HART – Single Ended
Function
The Analog Input Module is designed to accept high-level current inputs from transmitters and sensing devices.
Notable Features
- Extensive self-diagnostics
- Optional redundancy
- HART-capable, multivariable devices
- Fast loop scan
- Internal or external field power selection
- On board excitation power (no need for marshalling power)
- Suitable for Configure / Status for HART Device
- Galvanic Isolation
Detailed Specification - Analog Input with HART (8C-PAIHA1)
Parameter Specification
| Parameter | Specification |
|---|---|
| Input / Output Module | 8C-PAIHA1 - Analog Input with HART (16), Coated IOTA Modules |
| Input Type | Current (2-wire or self-powered transmitters) |
| Input Channels | 16 Channels (Single Ended type) |
| A/D Converter Resolution | 16 bits |
| Input Range 1 | 4-20 mA (through 250 Ω) |
| Voltage Rating | 24 VDC |
| Module Current Rating | 110 mA |
| Common Mode Rejection Ratio, dc to 60 Hz | 70 dB |
| Common Mode Voltage, dc to 60 Hz | -6 to +5 V peak |
| Normal Mode Rejection Ratio, at 60 Hz | 19 dB |
| Normal Mode Filter Response | Single-pole RC, -3 dB @ 6.5 Hz |
| Maximum Normal Mode Input | ± 30 Volts |
| Crosstalk, dc to 60 Hz | -60 dB |
| Maximum Input voltage | ± 30 Volts (any input referenced to common, no damage) |
| Input Scan Rate | 50 ms |
| Hardware Accuracy (@ CMV = 0 V) | ± 0.075% of full-scale (23.5°C ± 2°C) |
| ± 0.15% of full-scale (0 to 60°C) | |
| Galvanic Isolation | 1000VAC RMS or ±1000 VDC |
| Isolation Technique | Icoupler (in IOM) |
| Module Removal and Insertion Under Power | Supported |
| Transmitter Field Power Conditioning | Individually Protected Current Limiting Circuits. No fuse required |