Maximum Ratings
- OUTPUT VOLTAGE: Factory set at 24.0 V dc
Input Specifications
- Input Voltage Range: 85 to 265 V ac or 108 to 145 V dc, 125 V dc nominal (Refer to Table 1 and Table 3)
- Input Frequency Range: 47 to 63 Hz
- Input Current: 5.6 A at 85 V ac input (RMS maximum), 2.5 A at 230 V ac input (RMS maximum)
-
Efficiency (At Maximum Output Power):
- 77% minimum at 85 V ac input
- 85% typical at 120 V ac input
- 92% typical at 230 V ac input
- 90% typical at 240 V ac input
- Inrush Current: 20 A, at 110 V ac (peak at cold start), 40 A, at 220 V ac (peak at cold start)
-
Input Power:
- 453 W typical at 120 V ac, 50/60Hz
- 439 W typical at 230 V ac, 60 Hz
- 441 W typical at 230 V ac, 50 Hz
Output Specifications
- OUTPUT VOLTAGE: 24.0 V dc, ±0.2 V dc nominal factory setting (Refer to Table 1 and Table 2)
- VOLTAGE LINE REGULATION: 2.0% of Vout
- VOLTAGE LOAD REGULATION: 2.0% of Vout
- RIPPLE AND NOISE AT 20 MHZ: 100 mV (peak-to-peak), 10 mV (RMS maximum)
- TEMPERATURE COEFFICIENT: 0.025% per °C
- STARTUP TIME (SOFT-START): 3 s typical at 110 V ac input or 24 V dc, 5 s maximum
- OVERSHOOT: No overshoot at turn on, turn off, power failure or removal of short circuit
LOAD TRANSIENT RESPONSE:
- 50 to 100% LOAD CHANGE
- Recovery to within regulation limits within 50 ms
- Maximum output voltage excursion less than 5%
Protection Features
- OVER CURRENT PROTECTION: Current limiting to 110% of maximum at the rated 25°C load
- OVERVOLTAGE PROTECTION: Factory set at 28.0 V dc for DIN rail FBM/FCM/FCP applications
- FUSING (NON-USER ACCESSIBLE): 10 A slow-blow 250 V ac/V dc internal fuse
-
ISOLATION VOLTAGES:
- 3000 V ac input to output
- 500 V ac output to chassis ground
- 1500 V ac input to chassis ground
- LEAKAGE CURRENT: ac line to chassis ground is less than 1.6 mA when operated at 250 V ac (47 to 63 Hz) or lower voltages
- Vibration: 0.75 g (5 to 500 Hz)