P0922YU Foxboro I/A Series Power Supply 24VDC

In stock
Manufacturer:
Foxboro
Product No.:
P0922YU
Condition:
In Stock
Product Type:
Power Supply
Product Origin:
USA
Weight:
300g
Shipping port:
Xiamen
Warranty:
12 months

UBEST – Trusted Global Automation Parts Supplier

We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.

About Us | Contact

Maximum Ratings

  • OUTPUT VOLTAGE: Factory set at 24.0 V dc

Input Specifications

  • Input Voltage Range: 85 to 265 V ac or 108 to 145 V dc, 125 V dc nominal (Refer to Table 1 and Table 3)
  • Input Frequency Range: 47 to 63 Hz
  • Input Current: 5.6 A at 85 V ac input (RMS maximum), 2.5 A at 230 V ac input (RMS maximum)
  • Efficiency (At Maximum Output Power):
    • 77% minimum at 85 V ac input
    • 85% typical at 120 V ac input
    • 92% typical at 230 V ac input
    • 90% typical at 240 V ac input
  • Inrush Current: 20 A, at 110 V ac (peak at cold start), 40 A, at 220 V ac (peak at cold start)
  • Input Power:
    • 453 W typical at 120 V ac, 50/60Hz
    • 439 W typical at 230 V ac, 60 Hz
    • 441 W typical at 230 V ac, 50 Hz

Output Specifications

  • OUTPUT VOLTAGE: 24.0 V dc, ±0.2 V dc nominal factory setting (Refer to Table 1 and Table 2)
  • VOLTAGE LINE REGULATION: 2.0% of Vout
  • VOLTAGE LOAD REGULATION: 2.0% of Vout
  • RIPPLE AND NOISE AT 20 MHZ: 100 mV (peak-to-peak), 10 mV (RMS maximum)
  • TEMPERATURE COEFFICIENT: 0.025% per °C
  • STARTUP TIME (SOFT-START): 3 s typical at 110 V ac input or 24 V dc, 5 s maximum
  • OVERSHOOT: No overshoot at turn on, turn off, power failure or removal of short circuit

LOAD TRANSIENT RESPONSE:

  • 50 to 100% LOAD CHANGE
  • Recovery to within regulation limits within 50 ms
  • Maximum output voltage excursion less than 5%

Protection Features

  • OVER CURRENT PROTECTION: Current limiting to 110% of maximum at the rated 25°C load
  • OVERVOLTAGE PROTECTION: Factory set at 28.0 V dc for DIN rail FBM/FCM/FCP applications
  • FUSING (NON-USER ACCESSIBLE): 10 A slow-blow 250 V ac/V dc internal fuse
  • ISOLATION VOLTAGES:
    • 3000 V ac input to output
    • 500 V ac output to chassis ground
    • 1500 V ac input to chassis ground
  • LEAKAGE CURRENT: ac line to chassis ground is less than 1.6 mA when operated at 250 V ac (47 to 63 Hz) or lower voltages
  • Vibration: 0.75 g (5 to 500 Hz)