PM858 3BSE093350R1 ABB Processor Unit Module
Manufacturer:
ABB
Product No.:
PM858
Condition:
In Stock
Product Type:
Processor Unit Module
Product Origin:
Switzerland
Weight:
1200g
Shipping port:
Xiamen
Warranty:
12 months
UBEST – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
PM858 and TP830 Process Units
Main Features
- MPC866 Microprocessor running at 133 MHz.
- 16 MB RAM with internal and external battery backup capability.
- Direct connection to 12 x S800 I/O units via the electrical ModuleBus.
- Four integrated mainboard ports, including:
- CN1 + CN2, Ethernet ports (IEEE 802.3, 10BaseT)
- COM3, serial port (RS-232C) supporting modem functionality
- COM4, serial port (RS-232C) for service functions
- Other communication protocols achieved through expansion communication interface modules
- Redundancy scheme using Redundancy Control Link
- Compact Flash memory card for application and cold start data storage
Technical Data for Process Unit
| Item | Data |
|---|---|
| Memory | 4 MB flash PROM (for storing firmware), 16 MB SDRAM |
| Power Consumption | 5.1 W typical, 8.6 W typical (including all ModuleBus and CEX Bus power) |
| Current Consumption | 210 mA typical (360 mA maximum) (excluding ModuleBus and CEX-Bus power) |
| Power Input Terminals | 4-pole, screw-tightening terminals, L+, L–, SA, and SB |
| Power Requirements | Input design L+ and L–, 24 V nominal, voltage range between 19.2V DC and 30V DC |
| Redundant Power Supply Status Input | Input design SA, SB - Maximum input voltage 30 V - Minimum high-level input voltage 15 V - Maximum low-level input voltage 8 V |
| Power Backup | Process unit has an internal 5ms power backup capability, sufficient for CPU to handle controller power loss fault |
| Protection Level | IP20 compliant with EN60529, IEC 529 |
| Weight | 1200 g (2.6 lb) |
| Dimensions | W 119 x H 186 x D 135 mm (4.7 x 7.3 x 5.3 in.) |
Battery Technical Parameters
| Resource | Backup Time |
|---|---|
| Internal Battery | Minimum 158 hours |
| External Battery SB821 | Minimum 15 weeks |
| External Battery SB822 | Minimum 16 days when fully charged |
Electromagnetic Compatibility and Electrical Safety
PM858/TP830 complies with EMC Directive EMCD 2004/108/EC technical specifications.
Performance Data
The performance of the PM858 control unit is approximately 0.5 times that of the PM862 controller. When configured redundantly, the execution performance is slightly slower than in non-redundant configurations. The redundant controller switch-over time is generally less than 10ms.