Schneider Electric Modicon Premium TSXPSY8500M Power Supply Module – 75 W, 85–264 V AC
The TSXPSY8500M delivers stable power for Modicon Premium automation systems. This 75 W module accepts a wide AC input range from 85 V to 264 V. It outputs 5 V DC at 15 A and 24 V DC at 1.6 A for sensors. Engineers pick the TSXPSY8500M for its compact double-format design and full protection suite.
Core Power Ratings
- Brand: Schneider Electric
- Model: TSXPSY8500M
- Range: Modicon Premium Automation Platform
- Total Secondary Power: 75 W at 5 V DC
- 5 V DC Output: 15 A continuous
- 24 V DC Sensor Output: 1.6 A continuous
- Input Voltage 1: 85–140 V AC (nominal 100–120 V AC)
- Input Voltage 2: 170–264 V AC (nominal 200–240 V AC)
- Network Frequency: 50/60 Hz, limits 47–63 Hz
- Input Current: 1700 mA at 100 V; 500 mA at 240 V
- Inrush Current: 30 A at 100 V; 60 A at 240 V
- Module Format: Double
- Weight: 0.74 kg (1.63 lb)
Key Selling Points
- Wide dual-range AC input covers 85–140 V and 170–264 V networks worldwide.
- Internal 4 A time-delayed fuse protects the primary circuit from fault currents.
- Secondary circuit guards against overload, overvoltage, and short-circuit events.
- Delivers 100 W useful secondary power at 55 °C with an added fan module.
- Provides 85 W at 55 °C and 77 W at 60 °C without extra cooling.
- Three front LEDs show sensor voltage, output OK, and battery fault status.
- Insulation resistance exceeds 100 MOhm between primary and ground.
- Withstands 10 ms microbreaks without output loss.
- Double-format housing saves rack space in Premium platform racks.
Protection and Electrical Data
- Primary Fuse: Internal 4 A, 5 × 20 mm, time-delayed
- Overload Protection: Secondary circuit
- Overvoltage Protection: Secondary circuit
- Short-Circuit Protection: Secondary circuit
- I²t on Activation: 15 A²·s at 100 V; 8 A²·s at 240 V
- It on Activation: 0.15 A·s at 100 V and 240 V
- Dielectric Strength: 2000 V primary/earth; 2000 V primary/secondary
- Insulation Resistance: ≥100 MOhm primary/ground and primary/secondary
Environmental Immunity
- Operating temperature: 0–60 °C (32–140 °F)
- Storage temperature: -25–70 °C (-13–158 °F)
- Relative humidity: 10–95 % without condensation in operation
- Storage humidity: 5–95 % without condensation
- Operating altitude: 0–2000 m (0–6561 ft)
- Microbreak immunity: 10 ms
- Protective treatment: TC coating
- Ingress protection: IP20
- Pollution degree: 2
Installation Guide
- Slide the module into a Modicon Premium rack slot; it uses a double-format footprint.
- Connect the AC supply to the primary terminals; check the 47–63 Hz frequency range.
- Wire the 5 V DC 15 A output to the rack backplane per platform wiring rules.
- Wire the 24 V DC 1.6 A sensor supply to field sensors as needed.
- Confirm the green OK LED lights after power-up to verify output voltages.
- Watch the BAT LED; a red light signals a battery fault condition.
- Add a fan module to reach 100 W secondary power at 55 °C.
- Keep ambient temperature at or below 60 °C for rated output.
- Maintain pollution degree 2 and altitude under 2000 m for safe operation.
Package Contents
- 1 × Schneider Electric TSXPSY8500M power supply module
- 1 × protective packaging box
- Package dimensions: 26 × 18 × 9 cm
- Package weight: 1.026 kg (2.262 lb)
- Shipping via FedEx, UPS, or DHL
Frequently Asked Questions
- What input voltage ranges does the TSXPSY8500M accept? It takes 85–140 V AC and 170–264 V AC at 47–63 Hz for global use.
- How much 24 V sensor current can I draw? The module supplies 1.6 A at 24 V DC for field sensors.
- Does the module handle short circuits? Yes, it protects the secondary circuit against short circuits, overload, and overvoltage.
- What is the difference between 77 W and 100 W ratings? The 100 W rating needs a fan module at 55 °C; without it, output is 85 W at 55 °C and 77 W at 60 °C.
- What do the three front LEDs show? Green LEDs show sensor voltage and output OK; a red LED flags battery faults.