TSXDSY16S5 Schneider Electric Discrete Output Module

In stock
Manufacturer:
Schneider
Product No.:
TSXDSY16S5
Condition:
In Stock
Product Type:
Discrete Output Module
Product Origin:
DE
Weight:
310g
Shipping port:
Xiamen
Warranty:
12 months

UBEST – Trusted Global Automation Parts Supplier

We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.

About Us | Contact

Schneider Electric Modicon TSXDSY16S5 Discrete Output Module

The Schneider Electric TSXDSY16S5 is a 16-channel output module for TSX Micro PLC systems. It provides reliable AC switching for industrial loads like solenoids and contactors. This module uses triac-protected outputs for solid-state reliability. The TSXDSY16S5 operates on a wide AC voltage range for flexible application use.

Primary Product Specifications

  • Brand: Schneider Electric
  • Model: TSXDSY16S5
  • Product Line: Modicon TSX Micro / Premium Automation Platform
  • Module Type: Discrete (Digital) AC Output Module
  • Number of Outputs: 16 Channels
  • Output Type: Triac-Protected (Solid-State)
  • Output Voltage Range: 48...240 V AC (41...264 V AC per EN/IEC 61131-2)
  • Current per Channel: ≤ 1 A
  • Maximum Current per Module: ≤ 12 A (Total for all channels)
  • Response Time: < 10 ms (Activation and Deactivation)
  • Internal Current Consumption: 220 mA @ 5V DC
  • Module Net Weight: 0.31 kg (0.68 lb)

Electrical Protection & Safety Features

  • Short-Circuit Protection: Integrated 5 A Fast-Blow Fuse per Channel
  • Output Overload Protection: Integrated 5 A Fast-Blow Fuse per Channel
  • Output Overvoltage Protection: Ge-Mov (Metal Oxide Varistor) Suppressor
  • Isolation Resistance: > 10 MΩ at 500 V DC
  • Dielectric Strength: 2000 V AC, 50/60 Hz for 60 seconds
  • Ingress Protection (IP): IP20 (IEC 60529)
  • Pollution Degree: 2
  • Protective Treatment: Conformal Coating (TC)

Power & Thermal Management

  • Power Dissipation Formula: 0.85 W + (1 W x Number of Active Outputs x Current per Module)
  • Backplane Power: Supplied via the TSX base unit's 5V DC rail
  • Connection Type: Removable Screw Terminal Block
  • Terminal Tightening Torque: Follow standard TSX Micro specifications

Environmental & Operational Ratings

  • Operating Temperature: 0°C to +60°C (32°F to 140°F)
  • Storage Temperature: -25°C to +70°C (-13°F to 158°F)
  • Operating Humidity: 10% to 95% RH (non-condensing)
  • Storage Humidity: 5% to 95% RH (non-condensing)
  • Operating Altitude: 0 to 2000 meters (0 to 6561 ft)

Certifications & Standards Compliance

  • Safety Standards: UL 508, CSA C22.2 No 142, CSA C22.2 No 213 (Class I, Div 2, Groups A,B,C,D)
  • EMC Standards: Conforms to IEC 61131-2
  • Marine Certifications: ABS, BV, DNV, GL, LR, RINA, RMRS
  • Market Markings: CE Mark

Installation & Wiring Guidelines

  • Insert the module into an available slot on a compatible TSX Micro base unit.
  • Ensure the base unit's backplane can supply the required 220mA at 5V DC.
  • Use the removable screw terminal block for field wiring connections.
  • Connect each output channel to your AC load (lamp, solenoid, small contactor coil).
  • Do not exceed 1 A per channel or 12 A total for the entire module.
  • Provide proper external fusing or circuit protection for the main AC supply line.
  • Route AC power wires separately from low-voltage signal cables to minimize noise.

Packaging & Shipping Information

  • Package Contents: 1 x TSXDSY16S5 Output Module, 1 x Terminal Block (if not pre-installed)
  • Package Dimensions (L x W x H): 26.0 x 18.0 x 5.5 cm (10.2 x 7.09 x 2.2 in)
  • Package Gross Weight: 453 g (16.0 oz)
  • Shipping GTIN (EAN): 3389110876246
  • Shipping Methods: FedEx, UPS, DHL Express services available.
  • Return Policy: This electronic module is non-returnable.

Warranty & Support

  • Warranty Period: 12 months from the date of purchase.
  • Warranty covers defects in materials and manufacturing under normal operating conditions.
  • Installation must comply with all specified environmental and electrical limits.
  • Technical documentation is available for system integration and troubleshooting.

Frequently Asked Questions (FAQ)

  • What type of loads are triac outputs best suited for?

Triac outputs are ideal for switching AC loads like indicator lamps, small solenoid valves (AC coils), and relay coils. They offer fast, silent switching with no moving parts, unlike mechanical relay outputs.

  • Can I use this module to control a 24V DC load?

No, this is an AC output module only (48-240V AC). Using it with DC voltage will cause the triac to latch on permanently, potentially damaging the module and the load. Use a DC output module for DC loads.

  • What happens when the 5A internal fuse blows?

The fuse is not user-replaceable; it is integrated into the module's design. If a fuse blows due to a severe overload or short circuit, the individual output channel will stop working, and the entire module must be replaced.

  • How do I calculate the total heat generated by this module?

Use the formula: 0.85W + (1W x Number of Active Outputs x Current per Output). For example, with 8 outputs at 0.5A each: 0.85W + (1W x 8 x 0.5) = 4.85W total dissipation. Ensure your panel cooling can handle this.

  • Are the output channels isolated from each other?

The channels share a common AC supply connection. They are not individually isolated from each other but are optically isolated from the PLC's internal logic and backplane for safety and noise immunity.

© 2025 Ubest Automation Limited. All rights reserved.