Technical Specifications

Specification Details
PV Input Signals
  • Number of Inputs: 1
  • Input Type: Universal input system (selectable via software)
  • Sampling Period: 250 ms
  • Burnout Detection: Functionality for TC, RTD, and standard signals (0.4 to 2 V or 1 to 5 V)
  • Burnout condition: 0.1 V or less for standard signals
  • Input Bias Current: 0.05 µA (for TC or RTD b-terminal)
  • Measurement Current (RTD): Approximately 0.13 mA
  • Input Resistance: ≥ 1 MΩ for TC or mV input
  • Approximately 1 MΩ for DC voltage input
  • Allowable Signal Source Resistance: ≤ 250 Ω for TC or mV input (0.1 µV/Ω effect)
  • ≤ 2 kΩ for DC voltage input (≈ 0.01%/100 Ω effect)
  • Allowable Wiring Resistance (RTD input): Maximum 150 Ω/wire; 10 Ω/wire for -150.0 to 150.0 °C range
  • Wire resistance effect: ±0.1 °C/10 Ω
  • Allowable Input Voltage: ±10 V DC for TC, mV, or RTD input
  • ±20 V DC for DC voltage input
  • Noise Rejection Ratio: 40 dB (50/60 Hz) or more in normal mode
  • 120 dB (50/60 Hz) or more in common mode
  • Reference Junction Compensation Error: ±1.0 °C (15 to 35 °C)
  • ±1.5 °C (0 to 15 °C, 35 to 50 °C)
Loop Power Supply
  • Purpose: Supplies power to two-wire transmitters
  • Supply Voltage: 14.5 to 18.0 V DC (max. 21 mA)
  • 21.6 to 28.0 V DC (max. 30 mA for 24 V models)
  • Protection Circuit: Against field short-circuit
  • Operating Ambient Temperature: 0 °C to 40 °C (for 24 V DC loop power supply)
Retransmission Output
  • Number of Outputs: 1
  • Output Signal: 4-20 mA DC
  • Load Resistance: ≤ 600 Ω
  • Output Accuracy: ±0.3% of span under standard operating conditions (23 ±2 °C, 55 ±10% RH, power frequency of 50/60 Hz)
Contact Inputs
  • Purpose: Mode selection (target setpoints, Auto/Man modes)
  • Number of Inputs: 2
  • Input Type: Non-voltage contact or transistor open collector input
  • Input Contact Rating: 12 V DC, 10 mA or more
  • On/Off Determination: Non-voltage contact: ≤ 1 kΩ (on), ≥ 20 kΩ (off)
  • Transistor open collector: ≤ 2 V (on), leakage current ≤ 100 µA (off)
  • Minimum Status Detection Hold Time: Approximately 1 second
Contact Outputs
  • Purpose: Alarm output, FAIL output, and others
  • Number of Outputs: 3
  • Relay Contact Rating: 240 V AC/1 A or 30 V DC/1 A (COM terminal is common)
Dimensions Size: 48 (W) x 96 (H) x 100 mm