Schneider Electric Quantum DC Output Module 140DDO36400C

Na stanju
Manufacturer:
Schneider
Product No.:
140DDO36400C
Condition:
In Stock
Product Type:
DC Output Module
Product Origin:
DE
Weight:
450g
Shipping port:
Xiamen
Warranty:
12 months

UBEST – Pouzdan globalni dobavljač delova za automatizaciju

Nudimo širok asortiman industrijskih rezervnih delova za automatizaciju koji su dostupni na lageru. Svi proizvodi dolaze sa 12-mesečnom garancijom i 30-dnevnim povraćajem novca zbog problema sa kvalitetom.

O nama | Kontakt

Schneider Electric 140DDO36400C DC Output Module

The Schneider Electric 140DDO36400C is a high-density DC output module for the Modicon Quantum platform. This module provides ninety-six discrete output channels organized in six groups. It delivers reliable 24V DC switching for industrial control applications requiring numerous output points.

Core Technical Specifications

  • Brand: Schneider Electric
  • Model: 140DDO36400C
  • Product Line: Modicon Quantum Automation Platform
  • Module Type: 96-Channel DC Discrete Output (Sink)
  • Output Voltage: 24V DC Nominal (19.2 to 30V Range)
  • Output Logic: Negative Logic (Sink)
  • Addressing: Requires 6 Output Words
  • Bus Current: 250 mA @ 5V DC
  • Power Dissipation: 7 Watts
  • Net Weight: 0.45 kg (0.99 lbs)

Electrical Ratings & Performance

  • Channels per Group: 16 Channels (6 Groups Total)
  • Current per Point: ≤ 0.5 A Continuous
  • Current per Group: ≤ 3.2 A Continuous
  • Current per Module: ≤ 19.2 A Total
  • Surge Current: 2 A per Point
  • Voltage Drop: < 0.4 V @ 0.5 A
  • Leakage Current: ≤ 1 mA @ 24V (Off State)
  • Response Time: ≤ 0.1 ms (ON and OFF)
  • Isolation: 500 Vrms (Channel to Bus for 1 minute)

Protection & Diagnostic Features

  • Short-Circuit Protection: Yes (Built-in)
  • Overload Protection: Yes (Built-in)
  • Fault Indication: Fault Sensing and Reporting
  • Loss of Field Power: Detected and Reported
  • Channel Status: 96 Green LEDs (Output Status)
  • Module Status: 1 Green LED (Bus Active), 1 Red LED (External Fault)
  • Inductive Load Formula: L(H) = 0.5 / ((I(A))² × f(Hz)) for 0.5-4 Hz switching

Environmental & Compliance Data

  • Operating Temperature: 0 to 60°C (32 to 140°F)
  • Storage Temperature: -40 to 85°C (-40 to 185°F)
  • Operating Humidity: Up to 95% (non-condensing)
  • Operating Altitude: Up to 5000 meters (16404 feet)
  • EMC Immunity: 10 V/m (80-2000 MHz per IEC 801-3)
  • ESD Protection: 4 kV contact, 8 kV air discharge (IEC 801-2)
  • PCB Protection: Conformal coating (Humiseal 1A33)
  • Certifications: cUL, FM Class 1 Div 2, RMRS, C-Tick, GOST
  • Standards: UL 508, CSA C22.2 No.142, CE Marked

Packaging & Shipping Information

  • Package Includes: One Schneider Electric 140DDO36400C module
  • Shipping: Global delivery via FedEx, UPS, DHL
  • Standard industrial packaging ensures damage-free transport
  • Warranty: 12-month quality assurance period

Installation & Wiring Guidelines

  • Install the module in an enclosure maintaining the 0-60°C ambient range
  • Use proper 24V DC power supply within the 19.2-30V operational window
  • Do not exceed 0.5A continuous current per output channel
  • Implement appropriate fusing for each output group based on load requirements
  • Follow the inductive load formula for switching solenoids or relays above 0.5Hz
  • Ensure all field wiring uses correct gauge for the 0.5A load current
  • Maintain separation between DC output wires and analog signal cables
  • Verify all connections are secure to prevent voltage drop issues

Professional Questions & Answers

What does "negative logic (sink)" mean for wiring?

  • The module switches the negative side (0V) of the load. The load's positive side connects directly to the 24V DC supply, and the module provides the path to ground when activated.

How do I calculate heat dissipation for my cabinet?

  • The module dissipates a fixed 7W plus load-dependent heat. At full load (19.2A), total dissipation is approximately 7W + (19.2A × load voltage drop). Ensure adequate cabinet cooling for continuous operation.

Can I connect inductive loads directly to the outputs?

  • Yes, but you must calculate using the provided formula. For example, switching a 0.5A solenoid at 2Hz requires inductance below 0.25H. Always use suppression diodes or varistors for inductive loads.

What happens during a short circuit on one output?

  • The built-in protection limits the current and the module reports a fault. The specific channel's LED may indicate the issue, and the fault word in the controller can be programmed for system response.

Is this module suitable for high-speed switching applications?

  • With a 0.1ms response time, it can handle moderately fast switching. However, for very high frequencies above 4Hz with inductive loads, consult the inductance formula to avoid damage from voltage spikes.

© 2025 Ubest Automation Limited. All rights reserved.