Bently Nevada 3500/61-02-00 - External Termination System
UBEST – Proveedor Global de Piezas de Automatización Confiable
Ofrecemos una amplia gama de piezas de repuesto para automatización industrial en stock. Todos los productos cuentan con una garantía de 12 meses y un reembolso de 30 días por problemas de calidad.
Bently Nevada 3500/61-02-00 Temperature Monitor
- External Termination RTD/TC Monitor
- Six Channel Temperature Monitoring
- 4-20mA Recorder Outputs Included
- Full 12-Month Warranty Protection
External Termination Temperature Monitoring
The 3500/61-02-00 delivers precise temperature monitoring with external terminations. This industrial monitor provides reliable measurement for critical machinery protection.
Model Configuration Details
Complete Part Number: 3500/61-02-00
I/O Module Type: 02 = External Termination
Certification Level: 00 = Standard Approval
Manufacturing Origin: United States
Monitoring Capabilities
Multi-channel input - Up to 6 RTD or TC sensors
External termination - Flexible wiring options
High accuracy - ±1°C measurement precision
Current outputs - 4-20mA recorder signals
Dual alarms - Alert and Danger setpoints
Performance Specifications
Manufacturer: Bently Nevada
Model: 3500/61-02-00
Input Capacity: 6 RTD or thermocouple inputs
Power Usage: 9 watts typical consumption
Input Resistance: 10 MΩ per input lead
RTD Excitation: 925 μA current source
Output Signals: 4-20mA proportional outputs
Load Capacity: 0-600Ω, 0-12V compliance
Measurement Resolution: 1°C or 1°F
Accuracy Rating: ±1°C with external termination
Alarm Programming: 1-60 second delays
Operating Range: -30°C to +65°C
Storage Range: -40°C to +85°C
Module Weight: 0.91 kg (2.0 lb)
Rack Requirements: 1 front and 1 rear slot
Sensor Support
Thermocouple Types: E, J, K, T compatible
RTD Options: Platinum, Nickel, Copper
Temperature Coverage: -200°C to +1370°C
Wiring Methods: 3-wire and 4-wire RTDs
Protection Features
Alarm Types: Under and over temperature
Setpoint Range: 0-100% of full scale
Alarm Precision: 0.13% accuracy
Delay Settings: 1-60 seconds adjustable
Package Contents
1 x 3500/61-02-00 Monitor Module
Installation documentation
Compliance certification
Shipping & Service
Global express shipping via FedEx, UPS, DHL
12-month comprehensive warranty
Application engineering support
Technical Questions
What does external termination mean?
External termination allows connection to remote terminal blocks for flexible sensor wiring arrangements.
How many temperature points can it monitor?
The system monitors up to 6 separate temperature points using RTD or thermocouple sensors.
What output signals are provided?
It offers 4-20mA recorder outputs proportional to each channel's temperature reading.
How accurate are the measurements?
With external termination, accuracy reaches ±1°C at 25°C ambient temperature.
What alarm capabilities are included?
Programmable Alert and Danger alarms with time delays from 1 to 60 seconds.
© 2025 Ubest Automation Limited. All rights reserved.
Original Source: https://www.ubestplc.com/
Contact: sales@ubestplc.com | Phone: +86 180 3000 5825