Siemens Power Supply - SITOP PSU100S 6EP1332-2BA20

W magazynie
Manufacturer:
Siemens
Product No.:
6EP1332-2BA20
Condition:
In Stock
Product Type:
Power Supply
Product Origin:
USA
Weight:
500g
Shipping port:
Xiamen
Warranty:
12 months

UBEST – Zaufany Globalny Dostawca Części do Automatyki

Oferujemy szeroki wybór dostępnych od ręki części zamiennych do automatyki przemysłowej. Wszystkie produkty objęte są 12-miesięczną gwarancją oraz 30-dniowym zwrotem w przypadku problemów z jakością.

O nas | Kontakt

SITOP PSU100S 24VDC/2.5A Power Supply: Compact and Reliable Performance

Input Power Specifications

  • Input Voltage Range: 85-132V AC for 120V systems
  • Wide Input Capability: 170-264V AC for 230V operation
  • Frequency Range: 47-63 Hz automatic adaptation
  • Current Consumption: 1.25A at 120V, 0.74A at 230V input
  • Inrush Current Limit: Maximum 33A with 0.4 A²·s I²t value
  • Power Buffering: 20ms hold-up during voltage drops

Output Performance Characteristics

  • Stable DC Output: 24V DC nominal voltage rating
  • Adjustable Range: 22.8V to 28V via potentiometer control
  • Current Capacity: 2.5A continuous, 3A up to 45°C
  • Voltage Precision: 3% overall tolerance for consistent performance
  • Ripple & Noise: 30mV typical, 150mV maximum residual ripple
  • Response Time: 15ms typical voltage rise time

Protection & Safety Features

  • Overvoltage Protection: Internal cutoff below 33V output
  • Short-Circuit Proof: Constant current characteristic protection
  • Overload Capability: 150% rated current for 5 seconds
  • Current Limiting: 3.0-3.4A response range for fault conditions
  • Isolation Rating: SELV output per EN 60950-1 safety standards
  • Protection Class: IP20 for basic environmental protection

Efficiency & Thermal Management

  • High Efficiency: 85% typical energy conversion rate
  • Power Output: 60W typical delivered active power
  • Heat Dissipation: 10W typical power loss during operation
  • Temperature Derating: 3% per Kelvin above 60°C ambient
  • Parallel Operation: Supports 2 units for increased power
  • MTBF Rating: 1,804,044 hours at 40°C ambient temperature

Environmental Specifications

  • Operating Temperature: -25°C to +70°C wide range capability
  • Storage Conditions: -40°C to +85°C for transport and storage
  • Humidity Range: 5-95% non-condensing relative humidity
  • Climate Classification: IEC 60721 3K3 environmental category
  • Marine Approval: BV and DNV shipbuilding certifications
  • EMC Compliance: EN 61000-6-2 immunity and EN 55022 emission

Physical & Installation Data

  • Compact Dimensions: 32.5mm × 125mm × 120mm (W×H×D)
  • Installation Width: 32.5mm for space-efficient mounting
  • Mounting Height: 225mm including connection space
  • Lightweight Design: 0.32kg for easy handling
  • DIN Rail Mounting: EN 60715 35x7.5/15 snap-on installation
  • Wire Range: 0.5-2.5mm² for input and output connections

Monitoring & Indicators

  • Status Display: Green LED for 24V OK visual indication
  • Relay Contact: NO contact for remote monitoring (60V DC/0.3A)
  • Response Delay: Maximum 0.3s for status signal activation
  • Overshoot Protection: Less than 3% when switching on
  • Load Step Response: 1ms settling time for 10-90% changes
  • Voltage Stability: 0.1% regulation for input fluctuations

Package Contents

  • Complete 6EP1332-2BA20 power supply unit
  • DIN rail mounting clip and installation accessories
  • Operation manual and technical data sheet
  • Wiring diagram and connection guide
  • Pale turquoise device identification labels

Shipping & Delivery

  • FedEx express international shipping available
  • UPS worldwide expedited delivery options
  • DHL global air freight services offered
  • Secure professional packaging materials
  • Quick order processing within 24 hours

Technical Application Questions

  • What is the main advantage of this power supply's compact design?
  • The 32.5mm width allows high-density installation in control cabinets with limited space
  • How does the temperature derating affect practical applications?
  • Above 45°C ambient, the output current gradually reduces to maintain reliable operation
  • Can I use this unit in parallel configuration for redundancy?
  • Yes, two units can operate in parallel with proper bridging for increased reliability
  • What maintenance schedule ensures long-term reliability?
  • Annual inspection of terminals and cleaning of ventilation paths maintains optimal performance
  • How do I interpret the status relay contact signals?
  • The normally open contact closes when output voltage is within specification for remote monitoring

© 2025 Ubest Automation Limited. All rights reserved.